background image

– 27 –

Wiring for Radio Faults
You may program the radio fault output relay (refer to Programming the 7835C section) for either:

FAIL-SAFE mode (UL requirement)

Answer “Y” to “FLT REL ON (Y/N)”

Relay always energized [N.C.]

Relay will change state (and trigger a dialer, if
connected) in the event of power loss.

Fail-safe mode increases the standby current by about
10mA, which results in lower battery backup time
(about 15%) in the event of power loss.

LOW CURRENT mode

Answer “N” to “FLT REL ON (Y/N)”

Relay normally de-energized [N.O.]

Does not increase standby current

NOT approved for UL installations.

Run two wires from the 7835C’s radio fault terminals 11 and 12 to a zone on the control panel. Refer to the
Figures below for wiring the radio fault relay.

CONTROL PANEL

7835C

ZONE INPUT

2K or 3K (TYPICAL)

+

-

TERM. 11 
RADIO FAULT RELAY 1

TERM. 12 
RADIO FAULT RELAY 2

EOL RESISTOR

CONTROL PANEL

7835C

ZONE INPUT

2K or 3K (TYPICAL)

+

-

TERM. 11 
RADIO FAULT RELAY 1

TERM. 12 
RADIO FAULT RELAY 2

EOL RESISTOR

Figure 11.  Wiring the 7835C to trip a control panel zone 

Figure 12.  Wiring the 7835C to trip a

during a radio fault (required for UL installations)

control panel zone for normally open fault
(not UL approved)

AC Power Connections
Primary power for the 7835C is provided by a wall-mounted 16.5VAC / 40VA transformer ADEMCO PN:
1361 (1361CN in Canada).  Use of a transformer with a lower power rating will result in unreliable system
operation.

Connect the AC power wires from the 16.5V 40VA wall transformer to terminals 1 and 2 on the 7835C. Do
not plug the transformer into the AC power source until all wiring connections have been made and you are
ready to power up the 7835C. Refer to the 7835C Initial Power-Up Sequence section.

Backup Battery Connection
The optional battery backup (ADEMCO 7720BT) can provide over 4 hours of system life in the event of an
AC power failure.  When AC power is lost, the 7835C enters a low-power state and the programmable AC
loss message can alert the AlarmNet Control Center (AC loss messages are reported within 10-40 minutes
of actual AC loss). Any alarms that are tripped during this low-power state will wake the system up to
transmit the appropriate message.  After a successful transmission, the 7835C will reenter its low-power
state.  When the battery reaches 11.5V, a low-battery message is transmitted, which alerts the AlarmNet
Control Center that this may be the radio’s last message.  When the battery reaches 8.5V, radio
transmissions are no longer possible and the system shuts down. If AC power is restored before the system
shuts down, an AC Restore message will be sent and the battery will be recharged using the 7835C’s built-
in battery charger.  If AC power is restored after the system has shut down, a power-on reset condition
exists, and the radio will initialize itself as described earlier and the battery will be recharged.

The 7835C performs a battery test under load on a daily basis.  During this test, if the battery drops below
11.5V, a low-battery message will be generated to indicate that the battery should be replaced.

To install the battery, snap it into the battery holder with the connector wire towards the lower right. Do not
plug the battery in until all wiring connections have been made and you are ready to power up the 7835C.
Refer to 7835C Initial Power-Up Sequence section. When you are ready to power up the radio, plug the
battery connector into the battery jack located on the right-hand side of the 7835C terminal strip.

Lower cover must be in place for the 7835C to enter its lower power state during battery operation.

Содержание AlarmNet 7835C

Страница 1: ...HOOXODU RQWURO KDQQHO 7UDQVFHLYHU QVWDOODWLRQ DQG 6HWXS XLGH 12 352 1 352 5 00 5 66 5 675 7 21 237 21 K3204V2 8 99...

Страница 2: ...erica A Side B Side The FCC has divided the spectrum allocated to cellular communication between two carriers in each geographic location A and B The B side is operated by the local telephone company...

Страница 3: ...rol Center then logs the alarm and routes it via RF to the appropriate AlarmNet A or AlarmNet M equipped central station System Features Hardware Features Up to 6 input zones when ECP is not used that...

Страница 4: ...l with a single click test message refer to the Testing section for details b Test communication with the AlarmNet C network by double clicking the tamper test switch and receiving message validation...

Страница 5: ...27 0 Register radio must be programmed 11a Pulse Z3 Y N N Replacement radio must have PIN 11b Z3 Delay 00 127 0 12a Pulse Z4 Y N N 12b Z4 Delay 00 127 0 13a Pulse Z5 Y N N 13b Z5 Delay 00 127 0 14a Pu...

Страница 6: ...raph which is intended to be used as an installation tool and troubleshooting aid will become active LOCKING TAB LOCKING TAB Do not attempt to remove the upper cover There are no user serviceable comp...

Страница 7: ...or approximately 5 seconds followed by the RSSI bar graph green LEDs lighting in a chaser sequence from left to right After this power up sequence the Radio Status LEDs display solid green blinking ye...

Страница 8: ...ce request message un successful B side Red off MicroBurst coverage found B side 3 LED 3 blinking 7835C searching for MicroBurst coverage from the A side carrier Time to complete 1 5 minutes Green on...

Страница 9: ...signal 3 Find a location where the signal level is consistently better than 2 bars or 98dBm as measured with the 7720P The 7835C can function properly with the signal strength level as low as one hal...

Страница 10: ...st The yellow radio status LED blinks rapidly while waiting for validation Validation is a low priority receipt from AlarmNet to the 7835C and may take several minutes to receive If a message is not v...

Страница 11: ...wer Y Press SHIFT Y for YES answer SHIFT Press before pressing a SHIFT key function Will light SHIFT LED LED goes out once a key is pressed Press again for each SHIFT function desired 1 A 1 For enteri...

Страница 12: ...s to right Press N to enable voltage triggers for alarm input This question will NOT appear if you are programming via the control panel since ECP mode is automatically required Question 2 will be the...

Страница 13: ...red it will go back to the top of the list and try again If the radio remains out of coverage for 24 hours it will actively test for service as it did the first time it was powered up Auto Roam This m...

Страница 14: ...pulse detection on the zone is automatically disabled UL Questions 9 14 Select N for Pulse and 00 for Delay for UL installations Question 9 Pulse Z1 Y N Press Y if zone 1 is connected to a pulsed bel...

Страница 15: ...ne 6 is connected to a pulsed bell output Question 14b will appear If you press N the following appears Question 14a Z6 Delay 00 127 Enter the reporting delay from 1 127 seconds for zone 6 Enter 00 fo...

Страница 16: ...ate high goes low Question 23 Rest Z3 Y N Press Y to enable restoral reporting for zone 3 Press N to disable restoral reporting Question 23a Rest On CHG Y N Press Y if restore is to be sent when the t...

Страница 17: ...e designated for Telco fault reporting and one zone designated for tamper reporting Question 28 O C Zone Enter the open close reporting zone number 1 6 A 0 entry will not assign a zone to O C status m...

Страница 18: ...cond central station for zone 3 Enter N to disable reporting Question 40 2CS Z4 Y N Press Y to enable reporting to second central station for zone 4 Enter N to disable reporting Question 41 2CS Z5 Y N...

Страница 19: ...EW question If you are NOT programming the radio through a panel and no password has been assigned the following appears ENTER PASSWORD Y N Passwords can be used to split the programming questions int...

Страница 20: ...an take several minutes to complete Initiate the registration sequence by either clicking the tamper switch 3 times or by pressing shift and the up arrow on the 7720P If you are using a 7720P skip to...

Страница 21: ...sociated with this MIN in the AlarmNet database Registration Timed Out If no response to the registration request is received from AlarmNet this message will be displayed Reg Reject Bad ID PS If the C...

Страница 22: ...lpha numeric PIN that must be obtained by having an authorized person call the AlarmNet TAC Technical Assistance Center The PIN should be entered followed by the enter key Registration MSG1 Sent Regis...

Страница 23: ...unting holes must be used It is important to attach the unit securely so that it cannot be removed or accidentally knocked off the wall after installation SCREW SCREW MOUNTING HOLES WALL Figure 2 Moun...

Страница 24: ...e installation s configuration A C 1 A C 2 T R I G G E R V O L T A G E T R I G G E R G N D Z O N E 1 Z O N E 2 Z O N E 3 Z O N E 4 Z O N E 5 E C P I N Z O N E 6 E C P O U T R A D I O F A U L T R E L A...

Страница 25: ...voltage on each wire for different alarm conditions NOTE Trig must be connected to the control s electrical ground as shown in figures 6 7 8 9 and 10 and not to earth ground If the alarm control pane...

Страница 26: ...ion Instructions UL For UL ECP installations the 7835C must be connected to a Listed compatible control unit 7835C TERMINAL BLOCK ECP IN TERM 9 ECP OUT TERM 10 TRIG TERM 4 DATA OUT GND DATA IN CONTROL...

Страница 27: ...Sequence section Backup Battery Connection The optional battery backup ADEMCO 7720BT can provide over 4 hours of system life in the event of an AC power failure When AC power is lost the 7835C enters...

Страница 28: ...y consists of one yellow and four green LEDs arranged in a bar graph It indicates the signal strength at which the 7835C is receiving the local cell The display is intended as an installation aid for...

Страница 29: ...thin 90 seconds of a successful transmission it will retransmit the alarm The 7835C will continue to retransmit an unvalidated alarm once every 90 seconds until the message is validated or the old ala...

Страница 30: ...nnel xxx Sys x SID z xxxx Network System Display Channel xxx indicates the control channel that the 7835C is using to communicate with the local cell Sys x indicates the local carrier A side or B side...

Страница 31: ...mat codes above Ba Represents battery condition Battery voltage acceptable Battery voltage below 11 5V 5 V Battery voltage going low has not yet been sent to the central station appears only briefly X...

Страница 32: ...mounting location Refer to Selecting a Suitable Installation Site section Ensure the antenna connector is not damaged or obstructed Ensure the antenna is screwed down securely Low Battery message sen...

Страница 33: ...or antenna installed Reorient the receiving antenna until interference is reduced or eliminated Move the radio or television receiver away from the receiver control Move the antenna leads away from an...

Страница 34: ...m Systems 5 For all modes of operation residential burglar alarm installations must be in accordance with the National Electrical Code and UL1641 Installation and Classification of Residential Burglar...

Страница 35: ...35 127 6...

Страница 36: ...put triggering levels Zones 1 and 2 selectable GND or 4 5 to 14 2 volts into 10k ohms Zones 3 6 4 5 to 12 volts into 10k ohms RF power output 600mW Frequency band 833 835MHz Transmit 878 880MHz Receiv...

Страница 37: ...E L A Y 2 A U X R E L A Y 1 A U X R E L A Y 2 TRANSFORMER 16 5VAC 40VA ADEMCO 1361 ADEMCO 1361CN IN CANADA 1 2 3 4 TYPICAL CONTROL PANEL OUTPUT Bell Output Voltage Trigger Relay Module 5 6 7 8 9 10 11...

Страница 38: ...ABLE TO ANYONE FOR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES FOR BREACH OF THIS OR ANY OTHER WARRANTY EXPRESS OR IMPLIED OR UPON ANY OTHER BASIS OF LIABILITY WHATSOEVER EVEN IF THE LOSS OR DAMAGE IS CAU...

Отзывы: