ADEMCO AlarmNet 7835C Скачать руководство пользователя страница 11

– 11 –

 

6HFWLRQ3URJUDPPLQJWKH&

There are 3 methods of programming the 7835C: (1) Using a 7720P Programming Tool; (2)

 

using an ECP

capable control panel that supports long range radio programming,; (3) using the Programmerless
Registration Option (PRO).

To use the 7720P, connect the 7720P then power-up the radio. Refer to the description below.

To use an ECP capable control, connect the control, then power-up the radio. Select ECP operation by
pressing the tamper switch once while the radio status LEDs are flashing in unison, which toggles the
default configuration from zone mode to ECP mode. The unprogrammed 7835C flashes the radio status
LEDs as follows during initial power-up:

ECP mode = twice per second
Zone mode = once per second

The default device address of the radio is 3. Refer to the control’s instructions for programming procedures.

To use the Programmerless Registration Option, power-up the radio, then contact AlarmNet Technical
Assistance Center (TAC). Refer to the Programmerless Registration Option Installation and Programming
Guide insert.

Using a 7720P Programming Tool

The 7720P Programming Tool is powered by the 7835C via the Programming Jack. The 7835C will
automatically sense the presence of the 7720P when it is plugged in.

Each key of the 7720P has two possible functions: a normal function and a SHIFT function. To perform a
normal key function, simply press the desired key. To perform a SHIFT key function, press the SHIFT key,
then press desired function key.

Table 3. 7720P Normal & Shift Key (shift LED lit) Functions

   Key

Normal Key Function

SHIFT Key Function

BS/ESC

[BS]: Press to delete entry

[ESC]: Press to quit program mode;
also can reset EEPROM defaults*

/

[

]: Scroll down programming

[

]: Scroll up programming

N/Y

[N]: Press for "NO" answer 

[Y]: Press SHIFT-Y for "YES" answer

SHIFT

Press before pressing a SHIFT key function. Will light SHIFT LED. LED
goes out once a key is pressed. Press again for each SHIFT function desired.

1/A

[1]: For entering the number 1

[A]: For entering letter A

2/B

[2]: For entering the number 2

[B]: For entering letter B

3/C

[3]: For entering the number 3

[C]: For entering letter C

4/D

[4]: For entering the number 4

[D]: For entering letter D

5/E

[5]: For entering the number 5

[E]: For entering letter E

6/F

[6]: For entering the number 6

[F]: For entering letter F

7/S

[7]: For entering the number 7

[S]: For entering letter S

8/T

[8]: For entering the number 8

[T]: For entering letter T

9/X

[9]: For entering the number 9

[X]: For entering letter X

SPACE

[SPACE]: For scrolling option list

No SHIFT function

0

[0]: For entering the number 0

No SHIFT function

 #/ENTER

[#/ENTER]: Press to accept entries

No SHIFT function

* Active only when the "REVIEW?" prompt is displayed.

After connecting the 7720P cable, power up the 7835C .  The following will be displayed:

7835C x.xx

(c) Pittway 1999

x.xx 

current software revision level

   

NOTE: This document applies to software Rev. 1.23 or higher

At this prompt during initial power-up, you may proceed with programming the 7835C. Programming is
accomplished by answering displayed questions.  Most questions require only a [Y]es or [N]o response,
while others require a numerical response (ID numbers, etc.).  Press ENTER to accept each response and
proceed to the next question.  A "?" indicates an invalid entry.  The current value is displayed on the second
line in parentheses ( ).  To accept the current entry, simply press the ENTER key.  If the current value is an
invalid entry, pressing the enter key will cause the display to repeat the unanswered question; the next
question will not be displayed until a valid answer is entered.  Use the UP/DOWN arrow keys to scroll
through the programming questions without changing any values.  The ESC key will bring the list of
questions to the end.

Содержание AlarmNet 7835C

Страница 1: ...HOOXODU RQWURO KDQQHO 7UDQVFHLYHU QVWDOODWLRQ DQG 6HWXS XLGH 12 352 1 352 5 00 5 66 5 675 7 21 237 21 K3204V2 8 99...

Страница 2: ...erica A Side B Side The FCC has divided the spectrum allocated to cellular communication between two carriers in each geographic location A and B The B side is operated by the local telephone company...

Страница 3: ...rol Center then logs the alarm and routes it via RF to the appropriate AlarmNet A or AlarmNet M equipped central station System Features Hardware Features Up to 6 input zones when ECP is not used that...

Страница 4: ...l with a single click test message refer to the Testing section for details b Test communication with the AlarmNet C network by double clicking the tamper test switch and receiving message validation...

Страница 5: ...27 0 Register radio must be programmed 11a Pulse Z3 Y N N Replacement radio must have PIN 11b Z3 Delay 00 127 0 12a Pulse Z4 Y N N 12b Z4 Delay 00 127 0 13a Pulse Z5 Y N N 13b Z5 Delay 00 127 0 14a Pu...

Страница 6: ...raph which is intended to be used as an installation tool and troubleshooting aid will become active LOCKING TAB LOCKING TAB Do not attempt to remove the upper cover There are no user serviceable comp...

Страница 7: ...or approximately 5 seconds followed by the RSSI bar graph green LEDs lighting in a chaser sequence from left to right After this power up sequence the Radio Status LEDs display solid green blinking ye...

Страница 8: ...ce request message un successful B side Red off MicroBurst coverage found B side 3 LED 3 blinking 7835C searching for MicroBurst coverage from the A side carrier Time to complete 1 5 minutes Green on...

Страница 9: ...signal 3 Find a location where the signal level is consistently better than 2 bars or 98dBm as measured with the 7720P The 7835C can function properly with the signal strength level as low as one hal...

Страница 10: ...st The yellow radio status LED blinks rapidly while waiting for validation Validation is a low priority receipt from AlarmNet to the 7835C and may take several minutes to receive If a message is not v...

Страница 11: ...wer Y Press SHIFT Y for YES answer SHIFT Press before pressing a SHIFT key function Will light SHIFT LED LED goes out once a key is pressed Press again for each SHIFT function desired 1 A 1 For enteri...

Страница 12: ...s to right Press N to enable voltage triggers for alarm input This question will NOT appear if you are programming via the control panel since ECP mode is automatically required Question 2 will be the...

Страница 13: ...red it will go back to the top of the list and try again If the radio remains out of coverage for 24 hours it will actively test for service as it did the first time it was powered up Auto Roam This m...

Страница 14: ...pulse detection on the zone is automatically disabled UL Questions 9 14 Select N for Pulse and 00 for Delay for UL installations Question 9 Pulse Z1 Y N Press Y if zone 1 is connected to a pulsed bel...

Страница 15: ...ne 6 is connected to a pulsed bell output Question 14b will appear If you press N the following appears Question 14a Z6 Delay 00 127 Enter the reporting delay from 1 127 seconds for zone 6 Enter 00 fo...

Страница 16: ...ate high goes low Question 23 Rest Z3 Y N Press Y to enable restoral reporting for zone 3 Press N to disable restoral reporting Question 23a Rest On CHG Y N Press Y if restore is to be sent when the t...

Страница 17: ...e designated for Telco fault reporting and one zone designated for tamper reporting Question 28 O C Zone Enter the open close reporting zone number 1 6 A 0 entry will not assign a zone to O C status m...

Страница 18: ...cond central station for zone 3 Enter N to disable reporting Question 40 2CS Z4 Y N Press Y to enable reporting to second central station for zone 4 Enter N to disable reporting Question 41 2CS Z5 Y N...

Страница 19: ...EW question If you are NOT programming the radio through a panel and no password has been assigned the following appears ENTER PASSWORD Y N Passwords can be used to split the programming questions int...

Страница 20: ...an take several minutes to complete Initiate the registration sequence by either clicking the tamper switch 3 times or by pressing shift and the up arrow on the 7720P If you are using a 7720P skip to...

Страница 21: ...sociated with this MIN in the AlarmNet database Registration Timed Out If no response to the registration request is received from AlarmNet this message will be displayed Reg Reject Bad ID PS If the C...

Страница 22: ...lpha numeric PIN that must be obtained by having an authorized person call the AlarmNet TAC Technical Assistance Center The PIN should be entered followed by the enter key Registration MSG1 Sent Regis...

Страница 23: ...unting holes must be used It is important to attach the unit securely so that it cannot be removed or accidentally knocked off the wall after installation SCREW SCREW MOUNTING HOLES WALL Figure 2 Moun...

Страница 24: ...e installation s configuration A C 1 A C 2 T R I G G E R V O L T A G E T R I G G E R G N D Z O N E 1 Z O N E 2 Z O N E 3 Z O N E 4 Z O N E 5 E C P I N Z O N E 6 E C P O U T R A D I O F A U L T R E L A...

Страница 25: ...voltage on each wire for different alarm conditions NOTE Trig must be connected to the control s electrical ground as shown in figures 6 7 8 9 and 10 and not to earth ground If the alarm control pane...

Страница 26: ...ion Instructions UL For UL ECP installations the 7835C must be connected to a Listed compatible control unit 7835C TERMINAL BLOCK ECP IN TERM 9 ECP OUT TERM 10 TRIG TERM 4 DATA OUT GND DATA IN CONTROL...

Страница 27: ...Sequence section Backup Battery Connection The optional battery backup ADEMCO 7720BT can provide over 4 hours of system life in the event of an AC power failure When AC power is lost the 7835C enters...

Страница 28: ...y consists of one yellow and four green LEDs arranged in a bar graph It indicates the signal strength at which the 7835C is receiving the local cell The display is intended as an installation aid for...

Страница 29: ...thin 90 seconds of a successful transmission it will retransmit the alarm The 7835C will continue to retransmit an unvalidated alarm once every 90 seconds until the message is validated or the old ala...

Страница 30: ...nnel xxx Sys x SID z xxxx Network System Display Channel xxx indicates the control channel that the 7835C is using to communicate with the local cell Sys x indicates the local carrier A side or B side...

Страница 31: ...mat codes above Ba Represents battery condition Battery voltage acceptable Battery voltage below 11 5V 5 V Battery voltage going low has not yet been sent to the central station appears only briefly X...

Страница 32: ...mounting location Refer to Selecting a Suitable Installation Site section Ensure the antenna connector is not damaged or obstructed Ensure the antenna is screwed down securely Low Battery message sen...

Страница 33: ...or antenna installed Reorient the receiving antenna until interference is reduced or eliminated Move the radio or television receiver away from the receiver control Move the antenna leads away from an...

Страница 34: ...m Systems 5 For all modes of operation residential burglar alarm installations must be in accordance with the National Electrical Code and UL1641 Installation and Classification of Residential Burglar...

Страница 35: ...35 127 6...

Страница 36: ...put triggering levels Zones 1 and 2 selectable GND or 4 5 to 14 2 volts into 10k ohms Zones 3 6 4 5 to 12 volts into 10k ohms RF power output 600mW Frequency band 833 835MHz Transmit 878 880MHz Receiv...

Страница 37: ...E L A Y 2 A U X R E L A Y 1 A U X R E L A Y 2 TRANSFORMER 16 5VAC 40VA ADEMCO 1361 ADEMCO 1361CN IN CANADA 1 2 3 4 TYPICAL CONTROL PANEL OUTPUT Bell Output Voltage Trigger Relay Module 5 6 7 8 9 10 11...

Страница 38: ...ABLE TO ANYONE FOR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES FOR BREACH OF THIS OR ANY OTHER WARRANTY EXPRESS OR IMPLIED OR UPON ANY OTHER BASIS OF LIABILITY WHATSOEVER EVEN IF THE LOSS OR DAMAGE IS CAU...

Отзывы: