![ADB Safegate IDM 8000 Скачать руководство пользователя страница 56](http://html1.mh-extra.com/html/adb-safegate/idm-8000/idm-8000_user-manual_2847402056.webp)
SET SYSTEM HW SETTING
Step
Task
Remarks
1
Turn IDM 8000 main switch off
2
Remove MCU unit
3
Set SW1 disp switches to desired positions
4
Insert MCU and turn the main switch on
The settings can be viewed for checking from the display:
VIEW SYSTEM HW SETTING
Step
Task
Buttons
1
To open view/system select
View/More/More/Sys
2
Scroll displays until “DIP POS” is on Data field 2
Next.
SYSTEM HW SETTING DISPLAYS
See the column “view-value” in the “HW-settings” table to interpret the display values.
Header / function
Data 1
Data 2
Factory setting
Allowed range
System information
DIP POS
ABCD where
Project
A = U1 Nominal value code
0-3
B = F1 Nominal value code
0-1
C = Type code
0-7
D = Remote control code
0-3
4.6.8 System settings
General CCR settings are only enabled when the control switch is in Off-position.
Note
: ERR indication is provided if settings are not accepted.
•
CCR size: is used for output voltage calibration and scaling size dependent measurement data for remote monitoring.
•
CCR type: display only, normally set from HW-system settings. Can be set only if dip switch code enables setting from
display.
•
M-switch defines if the maintenance switch is used for earth fault maintenance or Lamp fault B reset (FAA-monitor reset)
function or is not used at all.
•
Monitor defines the indication operation mode. Realtime warnings and alarms are indicated only when the CCR is in
operation and the measurement is active. Latching: alarms and warnings are indicated after the alarm has been activated
even when the CCR has been in off state.
•
Password defines if the settings can be altered with or without asked password. Password is required with setting ON.
Factory setting is Off (No password needed). Factory setting of default password is 547.
•
No of lamps is used in lamp fault % indication and is provided for 2 directions.
•
Lamp rating; used only for information purposes, pre-set selections, provided for 2 directions.
IDM 8000
User Interface
44
Copyright
©
ADB Safegate, All Rights Reserved
Содержание IDM 8000
Страница 1: ...IDM 8000 CCR User Manual UM_IDM 8000 Rev 1 7 2021 05 06 ...
Страница 2: ......
Страница 8: ...IDM 8000 TABLE OF CONTENTS viii Copyright ADB Safegate All Rights Reserved ...
Страница 10: ...IDM 8000 List of Figures x Copyright ADB Safegate All Rights Reserved ...
Страница 12: ...IDM 8000 List of Tables xii Copyright ADB Safegate All Rights Reserved ...
Страница 18: ...IDM 8000 Safety 6 Copyright ADB Safegate All Rights Reserved ...
Страница 20: ...IDM 8000 About this Manual 8 Copyright ADB Safegate All Rights Reserved ...
Страница 76: ...IDM 8000 Troubleshooting 64 Copyright ADB Safegate All Rights Reserved ...
Страница 92: ...IDM 8000 Appendix F Parallel remote control example 80 Copyright ADB Safegate All Rights Reserved ...
Страница 100: ...IDM 8000 Appendix I Commissioning test report form 88 Copyright ADB Safegate All Rights Reserved ...
Страница 104: ...IDM 8000 Appendix J Spare part list 92 Copyright ADB Safegate All Rights Reserved ...
Страница 106: ...IDM 8000 Appendix K Components of electronics 94 Copyright ADB Safegate All Rights Reserved ...
Страница 107: ...Appendix L Appendix L CCR components UM_IDM 8000 Rev 1 7 2021 05 06 95 Copyright ADB Safegate All Rights Reserved ...
Страница 113: ...UM_IDM 8000 Rev 1 7 2021 05 06 101 Copyright ADB Safegate All Rights Reserved ...
Страница 114: ...IDM 8000 Appendix M Output Terminals 102 Copyright ADB Safegate All Rights Reserved ...
Страница 118: ......