I2 calibration
1. Connect external calibrated RMS A-meter (10A, accuracy better than 1%) in series with the load circuit. Use at least 10% load of the CCR
capacity.
Warning!
High voltage circuit – De-energize CCR before connecting!
Note : For more information on easy meter connection, see
in Appendix M – Ouput Terminals. Clamp meter
accuracy is normally not adequate for 1% accuracy. For periodic maintenance checks, clamp type meter is still recommended for safety reasons.
1. Select the second highest current step (approx. 5A).
1. Go to I2/U2 calibration: select Set/Cal/Out.
1. Adjust the I2 reading on datafield 1 to equal with the external meter reading.
1. Make sure that the readings are equal then select Set.
Warning!
Make sure that there is max 10% deviation between the two readings. Selecting set
with bigger difference between the readings may result to over current on the output
circuit!
1. Check that both readings are equal, if necessary repeat steps 4-6.
Note : I2 calibration affects also to VA-drop function.
Calibration with short circuit load (U2 = 0) is not allowed.
Calibration of more than ±10% from factory defaults is not allowed -> ERR indication in display.
U2 calibration
1. Connect external calibrated RMS V-meter (Min 30V, accuracy better than 1%) to the voltage transformer test
outputs located on the right side of the power unit of the control rack.
1. Select the maximum current step (6.6A).
1. Go to I2/U2 calibration: select Set/Cal/Out and then Next.
1. Check the external meter reading and adjust the U2 reading on data 1 to be equal with the external meter reading and then select Set .
Note : Round up to next bigger value e.g. 20.12->20.2.
1. Make sure that the both readings are equal and if necessary repeat step 4.
Note : U2 calibration affects also to VA-drop function
Calibration of more than ±10% from factory defaults is not allowed -> ERR indication in display.
4.4.2 Input Voltage U1 Calibration
Header / function
Data 1
Data 2
Remarks
U1 calibration
U1 / V
U1 Cal
+ - adjust
IDM 8000
User Interface
28
Copyright
©
ADB Safegate, All Rights Reserved
Содержание IDM 8000
Страница 1: ...IDM 8000 CCR User Manual UM_IDM 8000 Rev 1 7 2021 05 06 ...
Страница 2: ......
Страница 8: ...IDM 8000 TABLE OF CONTENTS viii Copyright ADB Safegate All Rights Reserved ...
Страница 10: ...IDM 8000 List of Figures x Copyright ADB Safegate All Rights Reserved ...
Страница 12: ...IDM 8000 List of Tables xii Copyright ADB Safegate All Rights Reserved ...
Страница 18: ...IDM 8000 Safety 6 Copyright ADB Safegate All Rights Reserved ...
Страница 20: ...IDM 8000 About this Manual 8 Copyright ADB Safegate All Rights Reserved ...
Страница 76: ...IDM 8000 Troubleshooting 64 Copyright ADB Safegate All Rights Reserved ...
Страница 92: ...IDM 8000 Appendix F Parallel remote control example 80 Copyright ADB Safegate All Rights Reserved ...
Страница 100: ...IDM 8000 Appendix I Commissioning test report form 88 Copyright ADB Safegate All Rights Reserved ...
Страница 104: ...IDM 8000 Appendix J Spare part list 92 Copyright ADB Safegate All Rights Reserved ...
Страница 106: ...IDM 8000 Appendix K Components of electronics 94 Copyright ADB Safegate All Rights Reserved ...
Страница 107: ...Appendix L Appendix L CCR components UM_IDM 8000 Rev 1 7 2021 05 06 95 Copyright ADB Safegate All Rights Reserved ...
Страница 113: ...UM_IDM 8000 Rev 1 7 2021 05 06 101 Copyright ADB Safegate All Rights Reserved ...
Страница 114: ...IDM 8000 Appendix M Output Terminals 102 Copyright ADB Safegate All Rights Reserved ...
Страница 118: ......