A.07.370e - Edition 2.0
Installation
6.10 Connect power input supply, big and small cabinet
The connection is based on screw terminals.
1. Strip the input power supply cables.
- 208-230V input
- up to 10 kVA: 16 mm
- from 10 to 30 kVA: 18 mm
- 380-400V input
- up to 15 kVA: 16 mm
- from 15 to 30 kVA: 18 mm
Connect - 1
1. Put the cables through the opening in the rear panel (A).
2. Connect the input supply cables to the terminals (B) and (C).
3. Connect the earthing wire to the terminal (D).
Connect - 2
1. Connect the earthing wire to the earthing network (A) of the
substation.
Input [V]
B
C
208-230
Phase
Neutral
380-400
Phase
Phase
A
B
C
D
A