Installation
6.7 Install additional earthing, stackable cabinet
1. Connect an earthing wire to the M8 earthing screw (A) at the
rear of the cabinet.
Use an earthing wire with a cross-section
of at least 10 mm². The wire must be as short as possible.
2. Connect the earthing wire to the earthing network of the
substation.
6.8 Install additional earthing, big and small cabinet
1. Connect an earthing wire to the M8 earthing screw (A).
Use
an earthing wire with a cross-section of at least 10 mm². The
wire must be as short as possible.
2. Connect the earthing wire to the earthing network of the
substation.
WARNING
Earth the cabinet correctly. The
equipment can create ground return
currents up to 3.5 mA. Also when the
equipment is not connected to the load,
the equipment can create lethal ground
currents.
A
Note
The procedure is not applicable when the equipment has a CS.
WARNING
Earth the cabinet correctly. The
equipment can create ground return
currents up to 3.5 mA. Also when the
equipment is not connected to the load,
the equipment can create lethal ground
currents.
A
Содержание CRE 10
Страница 1: ...A 07 370e Edition 2 0 Installation Manual Constant Current Regulator Type CRE ...
Страница 14: ...14 A 07 370e Edition 2 0 Safety ...
Страница 44: ...44 A 07 370e Edition 2 0 Inspection and transport ...
Страница 64: ...64 A 07 370e Edition 2 0 Installation ...
Страница 85: ...A 07 370e Edition 2 0 85 Technical data ...
Страница 86: ...adbsafegate com ...