Pre-installation
5.2.2
Substation specifications
- For details on the substation specifications below, see ICAO Aerodome Design Manual, Part 5 Electrical
Systems, DOC 9157-AN/901.
Table: 5.1
Substation specifications
Item
Description
Vault lighting
Well illuminated for used day and night. Obey the local regulations.
Shelter
- Clean and dry;
- Lockable;
- Fireproof;
- Separate construction with reinforced concrete floors and walls;
- Adequate drainage above ground level;
- Sufficient room and lighting for personnel to do maintenance work.
Location
- Reasonable distance from the control tower;
- Leaves limitation surfaces free;
- Vehicular access in all weather conditions;
- Minimum interference with aircraft traffic.
Ventilation
Install forced ventilation.
Electrical connections
- Sufficient number of conduits and cable entrance accesses;
- Sufficient power to supply all equipments;
- Access to the required power supply, remote control and series circuit cabling;
- Ground network;
- External fuse and an electrical distribution cabinet;
- Disconnection devices for the input and output current.
Содержание CRE 10
Страница 1: ...A 07 370e Edition 2 0 Installation Manual Constant Current Regulator Type CRE ...
Страница 14: ...14 A 07 370e Edition 2 0 Safety ...
Страница 44: ...44 A 07 370e Edition 2 0 Inspection and transport ...
Страница 64: ...64 A 07 370e Edition 2 0 Installation ...
Страница 85: ...A 07 370e Edition 2 0 85 Technical data ...
Страница 86: ...adbsafegate com ...