Installation and Commissioning Guide
Variable Capacity Commercial
41
Installation and Commissioning Guide- Package Ducted Variable Capacity Commercial
Doc. Part No. 0525-076 Ver. 3 210414
17. Indoor Fan Table And Fan Curve
17.01. PKV160T
NOTES
* Reduced fan airflow is the airflow during compressor OFF operation (optional feature)
W = Indoor Fan Power, Watts
PWM = Pulse Width Modulation Setting, % PWM (Adjustable through the LC7-2 Control Interface or Outdoor Board).
APPLICATION RANGE (COMPRESSOR ON)
AIRFLOW
(l/s)
EXTERNAL STATIC PRESSURE (Pa)
50
100
150
200
250
300
% PWM
W
% PWM
W
% PWM
W
% PWM
W
% PWM
W
% PWM
W
600
40
139
48
199
54
257
60
317
69
380
92
450
650
45
164
52
223
59
290
65
351
76
421
99
492
700
51
196
58
261
64
322
71
393
86
465
750
57
231
63
291
70
362
78
443
95
509
800
62
259
70
339
77
413
84
485
850
69
304
77
387
83
459
94
539
900
76
349
83
431
89
507
MOTOR / BLOWER LIMIT
REDUCED AIRFLOW *(COMPRESSOR OFF)
AIRFLOW
(l/s)
EXTERNAL STATIC PRESSURE (Pa)
50
100
150
200
250
300
% PWM
W
% PWM
W
% PWM
W
% PWM
W
% PWM
W
% PWM
W
200
22
87
27
123
31
150
250
21
73
26
108
30
139
35
181
44
220
300
24
85
29
121
34
162
38
197
51
245
350
21
61
27
98
33
142
38
184
43
223
58
279
400
22
64
30
109
36
155
42
206
48
255
64
306
450
27
82
34
129
40
176
46
228
53
284
70
338
500
31
98
38
149
44
197
51
259
58
316
76
373
550
36
122
42
169
49
227
55
282
63
346
84
411
MOTOR / BLOWER LIMIT
Default Fan Speed Value at 100Pa
Speed
Default PWM (adjustable)
High PWM (%)
83
Medium PWM (%)
63
Low PWM (%)
48
Indoor Fan PWM Limits
PWM High Limit
99
PWM Low Limit
40