Installation and Commissioning Guide
Variable Capacity Commercial
43
Installation and Commissioning Guide- Package Ducted Variable Capacity Commercial
Doc. Part No. 0525-076 Ver. 3 210414
17.02. PKV180T
NOTES
* Reduced fan airflow is the airflow during compressor OFF operation (optional feature)
W = Indoor Fan Power, Watts
PWM = Pulse Width Modulation Setting, % PWM (Adjustable through the LC7-2 Control Interface or Outdoor Board).
REDUCED AIRFLOW *(COMPRESSOR OFF)
AIRFLOW
(l/s)
EXTERNAL STATIC PRESSURE (Pa)
50
100
150
200
250
300
% PWM
W
% PWM
W
% PWM
W
% PWM
W
% PWM
W
% PWM
W
200
11
35
18
63
23
96
28
132
32
163
37
203
250
16
48
21
76
26
110
31
148
36
188
45
230
300
18
53
24
87
30
129
34
162
39
206
51
250
350
21
63
28
106
33
142
39
192
44
235
57
285
400
23
66
31
117
37
163
43
214
48
257
64
300
450
28
89
35
137
41
184
47
235
54
295
69
348
500
32
105
39
157
45
204
52
266
59
324
76
386
550
36
122
43
175
50
233
56
288
64
357
83
426
600
41
146
48
201
55
261
61
322
69
389
91
469
APPLICATION RANGE (COMPRESSOR ON)
AIRFLOW
(l/s)
EXTERNAL STATIC PRESSURE (Pa)
50
100
150
200
250
300
% PWM
W
% PWM
W
% PWM
W
% PWM
W
% PWM
W
% PWM
W
680
50
191
57
254
64
320
71
391
81
456
700
52
201
59
265
66
333
73
405
85
475
750
58
236
65
303
72
372
79
445
93
524
800
64
271
71
340
79
422
86
499
850
71
315
78
386
85
468
94
558
900
78
360
85
440
93
528
950
85
412
93
499
1000
93
467
1020
96
489
MOTOR / BLOWER LIMIT
Default Fan Speed Value at 100Pa
Speed
Default PWM (adjustable)
High PWM (%)
99
Medium PWM (%)
78
Low PWM (%)
57
Indoor Fan PWM Limits
PWM High Limit
99
PWM Low Limit
50
Содержание PKV160T
Страница 57: ...THIS PAGE WAS INTENTIONALLY LEFT BLANK ...
Страница 58: ...THIS PAGE WAS INTENTIONALLY LEFT BLANK ...
Страница 59: ...THIS PAGE WAS INTENTIONALLY LEFT BLANK ...