Installation and Commissioning Guide - Package Ducted Variable Capacity Commercial
Doc. Part No. 0525-076 Ver. 3 210414
Installation and Commissioning Guide
Variable Capacity Commercial
28
Option 1: Via LC7-2 Wall Control
Summary :
If required, adjust the
PWM
of 1-Speed Setting
If required, adjust the
LOW
PWM
of 3-Speed Setting
If required, adjust the
HIGH RPM
of 3-Speed Setting
Enable / Disable
CONTINUOUS
Fan Setting
Select
1-Speed
or
3-Speed
Indoor Fan
If required, adjust the
LOW
RPM
of 3-Speed Setting
If required, adjust the
HIGH
PWM
of 3-Speed Setting
If required, adjust the
REDUCED AIRFLOW
Setting
EXIT
Service Menu
Enter Service Menu
Select
Menu 03
If required, adjust the
MED
PWM
of 3-Speed Setting
If required, adjust the
MED
RPM
of 3-Speed Setting
If required, adjust the
DEFROST FAN
Setting
If required, adjust the
HOT START FAN
Setting
Procedure:
1. Press and hold the
REPEAT
and the
TIMER
buttons for 3 seconds then release to enter Service Menu.
2. Press the
button to scroll through to Service Menu
03
.
3. Press the
PROG
button to enter Service Menu
03
. Display will show the indoor fan speed selection.
NOTES
1 Speed indicated with number
1
and
MED
being illuminated.
3 Speed indicated with number
3
and
LOW
,
MED
and
HIGH
being illuminated.
1- Speed Indoor Fan DEFAULT
3- Speed Indoor Fan