Installation and Commissioning Guide
Variable Capacity Commercial
33
Installation and Commissioning Guide- Package Ducted Variable Capacity Commercial
Doc. Part No. 0525-076 Ver. 3 210414
3. Press the
PROG
button 11x times to enter the Hot Start Settings.
4. Press the
or
buttons to enable/disable the hot start operation.
5. Press the
PROG
button to accept the Hot Start setting.
6. Press the
EXIT
button once to return to the Main Screen.
15.04.05. Air Filter Hours
This feature allows the installer to change the alarm time of Filter Notification. By default, the time before the filter
alarm notification will appear is set to
200
hours. This is adjustable from
0
to
990
hrs.
Outdoor Unit CPU Board
1. Using the
MENU
and the
ENTER
buttons, navigate to
SEt
(Settings)
→
iduS
(Indoor Settings)
→
FiL
(Filter)
2. Keep pressing the
MENU
button to select the desired filter notification alarm time is shown. By default, alarm
time is set to
200
hrs and is adjustable from
0
to
990
Note:
0
means the Filter Alarm is disabled
3. Press
ENTER
to confirm the alarm time settings.
4. Press the
BACK
button twice to go back to the original status display.
15.04.06. Economy Damper
This feature allows to set the optional outside air damper opening. The available output signal is from
0
to
10
V.
Option 1: LC7-2 Wall Control
1. Press and hold the
REPEAT
and the
TIMER
buttons for 3 sec then release to enter Service Menu. The display will
show the Service Menu
01
.
2. Press the
or
buttons to scroll to Service Menu
10
. Press the
PROG
button to enter the Service Menu
10
.
3. Press the
PROG
button enter economy damper menu.