Installation and Commissioning Guide - Package Ducted Variable Capacity Commercial
Doc. Part No. 0525-076 Ver. 3 210414
Installation and Commissioning Guide
Variable Capacity Commercial
20
12. Package Unit Electrical Connection
THREE PHASE MAINS WIRING (400 VAC)
( Three Phase +Earth) 50Hz
DATA CABLE TO WALL CONTROL
(Cat5E UTP (AWG 24) Data Cable)
1
2
DETAILED WIRING DIAGRAM IS PROVIDED WITH THE UNIT
Condenser Side: Located at the back of electrical/compressor access panel.
WALL
CONTROL
SUB-MAINS
CIRCUIT BREAKER
(Field Supplied by Installer)
DATA CABLE
(Field Supplied by Installer)
2
PACKAGE UNIT
MAIN SUPPLY FROM
DISTRIBUTION BOARD
SUB-MAIN
TO UNIT
SUB-MAINS
ISOLATOR
(Field Supplied by Installer)
1
CIRCUIT BREAKER SIZE AND CABLE SIZE REQUIREMENT
Model
Circuit Breaker Size
Cable Size * (mm
2
)
Amps
Main
PKV160T
20.0
2.5
PKV180T
20.0
2.5
PKV210T
25.0
4.0
PKV240T
25.0
4.0
* Suggested Minimum Cable Size should be used as a guide only. Larger size cables may be required
dependent on installation method, length of cables and ambient temperature. Refer to the latest
edition of the AS/NZS 3000 “Australian / New Zealand Wiring Rules” for more details.