Installation and Commissioning Guide - Package Ducted Variable Capacity Commercial
Doc. Part No. 0525-076 Ver. 3 210414
Installation and Commissioning Guide
Variable Capacity Commercial
18
10. Condensate and Safety Tray Drainage Instructions
NOTES
• Parts for the Condensate Trap are not supplied with the unit.
SUGGESTED DRAIN TRAP DETAILS
Ensure Drain Pipe slopes down
from the unit at a minimum of
10mm per metre
DETAIL A
The top of the Trap must
be 125mm below the top
of the Evaporator Drain
Connection
50mm
4 x PVC
Elbow
Install a T-Piece
as an Air Vent
for long drain runs
Hose
Clamps
Condensate Tray
The top of the Vent must be
50mm higher than the top of
the Evaporator Condensate Tray
250mm or high enough to
maintain positive Air Seal
Condensate Drain
Connection
DN 25mm PN12
Trap
Clear
Plastic
Inspection
Tube
125mm
NOTES
• PKV model shown for illustration purposes only.
• Ensure that Condenser and Evaporator condensate
drains are connected separately.
A
Ensure Condensate Drain Connection Drain Pipe slopes
down from the unit at a minimum of 10mm per metre.
Seal with
Silicon Sealant
Ensure
Drain Connection Drain
Pipe slopes down from the unit at
a minimum of 10mm per metre.
COMP
INDOOR
FANS
INDOOR
FANS
MOTOR
OUTDOOR COIL
TOP VIEW
FRONT VIEW
PKV210-240T-T
Содержание PKV160T
Страница 57: ...THIS PAGE WAS INTENTIONALLY LEFT BLANK ...
Страница 58: ...THIS PAGE WAS INTENTIONALLY LEFT BLANK ...
Страница 59: ...THIS PAGE WAS INTENTIONALLY LEFT BLANK ...