BusWorks Model XT1531‐000
4 CH Current 4 CH Digital I/O w/USB & Modbus
Acromag, Inc. Tel: 248‐295‐0880
‐
7
‐
Power Connections
Connect a DC power supply from 12‐32V as shown in the drawing below. Observe
proper polarity (input power is reverse‐polarity protected). Optionally, the unit
may
be powered (or redundantly powered) via its DIN rail connector (optional terminal
required, see bottom figure below). For supply connections, use 14 AWG wire rated
for at least 80°C. Do not exceed 36V DC peak. Note that output channels of this
model will require separate connections to power (see Output Connections).