Installation
64/ 80
LipuJet-P-OB / -OD, LipuJet-P-OA / -OAP
4.8 Electrical connection and collective fault
signal (LipuJet-P-OA, -OAP)
Installation of a CEE mains socket for
the control
The switch box (protection type IP 54) are
supplied with a 5 m long cable with CEE
mains plug / 16 A ready for connection.
A relevant CEE mains socket has to be
fitted locally.
Connecting value: 400 V / 50 Hz
Fuse: 3 x 16A, slow-blowing
Switch box (controls): transmission of collective fault signal
The switch box includes a potential-free contact for transmission of a collective fault
signal to a building monitoring system.
Please check the relevant wiring option in the terminal diagram, see separate document.