93
UK
18 Troubleshooting
The alarm centre shows no reaction
although mains and battery power are
present.
Check mains and battery connections and the three fuses. Replace fuses with
fuses of similar rating if necessary.
The display shows one or more open
zones (although all alarm contacts
seem to be at rest) and the alarm
centre cannot be activated or there is
no permanent error tone.
Remove all connections of the alarm zone concerned and replace them by a wire
jumper between CCT. If the zone is displayed as closed, the cause of the problem
is in the connected alarm contacts/cables. Check them using a circuit tester.
There may be a short-circuit between the alarm and tamper zone or the 0V
contact.
The alarm centre reports continuous
tampering.
Check the tamper contacts of the alarm centre and the control units. The springs
of these contacts must be pressed in fully. Check the connected tamper contacts
with a circuit tester and make sure there is no short-circuit. Make sure that the
tamper zone of the siren is also terminated with 0V.
The triggering of a sensor does not
result in an alarm.
If you have connected more than one sensor in an alarm line, check that all NC
contacts are connected serially and not in parallel, then activate all connected
sensors simultaneously. Make sure that you have removed the wire jumper of the
zones that was fitted in the factory. Has the alarm zone been correctly
programmed?
External alarm does not start.
Use a multimeter to check the transistor output to which n the siren is connected
to ensure correct functioning of the alarm centre. Then connect the siren directly
to the battery and check its function.
Tamper alarm is not triggered
although a tamper contact was
opened on an alarm sensor.
Check that all tamper contacts are connected in series. If they are connected in
parallel, all contacts must first be opened to trigger a tamper alarm. There may be
a short-circuit in the wiring.
Sensors trigger a false alarm.
Check that the sensors have been installed and adjusted according to the
manufacturer’s instructions. In the case of motion sensors, check that they have
been mounted to face into the room and not towards any heat source. In the case
of door/window opening contacts, check that the switching distance between the
reed contact and the magnet does not have too much movement. Check the
wiring. Check that solder joints and clamps are sound. If cables are laid too near
to high-voltage lines, errors can also occur.
Program and user code forgotten.
Disconnect mains and auxiliary power supply from the alarm centre. Short-circuit
the “NVM RST” jumper under the connector block of the additional transistor
outputs and then, with the jumper still short-circuited, reconnect the auxiliary
power supply and then the mains supply. All code and chip keys deleted. The
user code 1 (master code) is reset to 1234, and the installer code 7890. The
programming, except for date/time, remains intact.
You think the alarm centre has a
malfunction.
Restore the factory settings (program menu option 98) and check the function
again. The fault is usually in the external cabling.
Содержание Terxon MX
Страница 10: ...10 D 8 bersicht der Geh usekomponenten 2 4 6 5 3 7 1 8 9...
Страница 104: ...104 D...
Страница 114: ...10 UK 8 Overview of housing components 2 4 6 5 3 7 1 8 9...
Страница 149: ...45 UK Entry delay group 2 202 n See 201 Entry delay group 3 203 n See 201 Entry delay group 4 204 n See 201...
Страница 210: ...10 FR 8 Vue d ensemble des composants du bo tier 2 6 3 7 1 8 9 4 5 FR...
Страница 314: ...10 NL 8 Overzicht van de componenten van het huis 2 6 3 7 1 8 9 NL...
Страница 320: ...16 NL Aansluitingen voor telefoonaansluiting RJ11 A B A1 B1 RJ11 aansluiting schroefaansluitingen voor telefoonleiding...
Страница 381: ...77 NL Wijzigen van het volume bij een intern alarm 46 Zone instelling 44 Zonesabotage 49...
Страница 392: ...10 DK 8 Oversigt over kabinetkomponenterne 2 4 6 5 3 7 1 8 9...
Страница 484: ...102 DK...