076 Behaviour of exit mode internal (D)
To change the property of the exit mode for internal active
(D):
1. On the control unit, enter:
076
2. The LCD display shows: 076: D=Low Tone
3. Via the keypad, select from the following items
and press:
0
D=Low Tone
The acoustic signal during the exit
delay time is emitted at half volume.
1
D=Instant
During internal activation, the alarm
centre is internally activated
immediately – i.e., without delay.
2
D=Silent
No acoustic signal is emitted during the
delay time. Following expiry of the delay
time, the alarm centre emits a brief
signal.
3
D=A
The initial mode for internal active B is
as for the initial mode of overall active A
In a partitioned system
0
D=Timed
Activation of partition D after exit time
(command 79). A connected key switch
at the control unit shortens the exit time
when activated
1
D=Terminated
Activated via key switch connected to
the control unit. The exit time is
unlimited.
2
D=Final Door
Activation of the partition by closing the
last door detector
3
D=Instant
Active without delay time
4
D=Silent
Use command 79 for the exit time. The
control unit emits a double beep when
the time has expired.
5
D=Lock Set
Key switch (see command 39)
4. Confirm your input. On the control unit, enter:
.
5. The control unit acknowledges your input with a
double “beep” tone and shows Installer Mode.
077 Alarm behaviour for internal (D)
To change the alarm property for internal active (D):
1. On the control unit, enter:
077
2. The LCD display shows: 077: D = Internal
3. Via the keypad, select from the following items
and press:
0
D=Keypad
Only the control units are activated.
1
D=Internal
On alarm, the control units and the
internal alarm are activated.
2
D=Local
On alarm, the control units, the internal
alarm and the external siren are
activated.
3
D=Full
On alarm, the control units, the internal
signalling, the external sirens and the
exits are activated.
In a partitioned system
0
D=Keypad
Only the control units are activated.
1
D=Local
On alarm, the control units, the internal
alarm and external sirens are activated.
2
D=Full
Control unit + in ex
telephone dialler
4. Confirm your input. On the control unit, enter:
.
5. The control unit acknowledges your input with a
double “beep” tone and shows Installer Mode.
Содержание Terxon MX
Страница 10: ...10 D 8 bersicht der Geh usekomponenten 2 4 6 5 3 7 1 8 9...
Страница 104: ...104 D...
Страница 114: ...10 UK 8 Overview of housing components 2 4 6 5 3 7 1 8 9...
Страница 149: ...45 UK Entry delay group 2 202 n See 201 Entry delay group 3 203 n See 201 Entry delay group 4 204 n See 201...
Страница 210: ...10 FR 8 Vue d ensemble des composants du bo tier 2 6 3 7 1 8 9 4 5 FR...
Страница 314: ...10 NL 8 Overzicht van de componenten van het huis 2 6 3 7 1 8 9 NL...
Страница 320: ...16 NL Aansluitingen voor telefoonaansluiting RJ11 A B A1 B1 RJ11 aansluiting schroefaansluitingen voor telefoonleiding...
Страница 381: ...77 NL Wijzigen van het volume bij een intern alarm 46 Zone instelling 44 Zonesabotage 49...
Страница 392: ...10 DK 8 Oversigt over kabinetkomponenterne 2 4 6 5 3 7 1 8 9...
Страница 484: ...102 DK...