TZIDC-200, TZIDC-210, TZIDC-220
DIGITAL POSITIONER | 42/18-85-EN REV. E
11
IECEx – ‘Ex i’ type of protection
Ex marking
Marking
Ex ia IIC T6 or T4 Gb
Ex ib IIC T6 or T4 Gb
Type Examination Test Certificate
IECEx TUN 04.0015X
Type TCIDC-200
Standards IEC
60079-0
IEC 60079-11
IEC 60079-15
Temperature Data
Temperature class
Ambient temperature Ta
T4
−
40 to 85 °C
T6*
−
40 to 40 °C*
* When using the ‘Limit Monitor’ plug-in module in temperature class T6, the
maximum permissible ambient temperature range is
−
40 to 35 °C
(
−
40 to 95 °F).
Electrical Data
In intrinsically safe explosion protection types Ex ib IIC / Ex ia IIC,
only for connection to a certified intrinsically safe circuit.
Current circuit (terminal)
Electrical information (maximum values)
Signal circuit
(+11 /
−
12)
U
i
= 30 V
I
i
= 320 mA
P
i
= 1.1 W
C
i
= 6.6 nF
L
i
= negligibly small
Contact input
(+81 /
−
82)
U
i
= 30 V
I
i
= 320 mA
P
i
= 1.1 W
C
i
= 4.2 nF
L
i
= negligibly small
Switch output
(+83 /
−
84)
U
i
= 30 V
I
i
= 320 mA
P
i
= 500 mW
C
i
= 4.2 nF
L
i
= negligibly small
Local communication interface
(LCI)
Only for connection to a programming device
outside the hazardous area (see special
conditions).
The following modules may be operated as an option:
Current circuit (terminal)
Electrical information (maximum values)
Plug-in module for digital
position feedback
(+51 /
−
52)
(+41 /
−
42)
U
i
= 30 V
I
i
= 320 mA
P
i
= 500 mW
Ci = 3.7 nF
Li = negligibly small
Plug-in module for analog
position feedback
(+31 /
−
32)
U
i
= 30 V
I
i
= 320 mA
P
i
= 1.1 W
Ci = 6.6 nF
Li = negligibly small
Special conditions
• Devices must only be connected to circuits in zone 2 if they
are suitable for operation in zone 2 potentially explosive
atmospheres and for the conditions prevailing at the
installation location (manufacturer's declaration or
certificate from an inspection authority).
• For the ‘Limit monitor with proximity switches’ circuit,
measures outside of the device must be implemented to
prevent the rated voltage from being up-scaled by more than
40 % due to transient disturbances.
• It is only permissible to connect, disconnect, and switch live
circuits during installation or maintenance, or for the
purpose of carrying out repairs. Note: It is considered very
unlikely that a potentially hazardous atmosphere would be
present in zone 2 at the same time that installation or
maintenance or repair work was being carried out.
• Only non-flammable gases must be used for pneumatic
power supply.
• Only suited cable entries must be used that meet the
requirements of EN 60079-15.
• The local communication interface (LCI) for the TZIDC and
the TZIDC-200 may only be operated at U
m
≤
30 V GS outside
the hazardous area.
Содержание TZIDC-200
Страница 59: ...TZIDC 200 TZIDC 210 TZIDC 220 DIGITAL POSITIONER 42 18 85 EN REV E 59 FM installation drawing No 901176...
Страница 61: ...TZIDC 200 TZIDC 210 TZIDC 220 DIGITAL POSITIONER 42 18 85 EN REV E 61...
Страница 63: ...TZIDC 200 TZIDC 210 TZIDC 220 DIGITAL POSITIONER 42 18 85 EN REV E 63 FM installation drawing No 901265...
Страница 65: ...TZIDC 200 TZIDC 210 TZIDC 220 DIGITAL POSITIONER 42 18 85 EN REV E 65 Change from one to two columns...
Страница 67: ...TZIDC 200 TZIDC 210 TZIDC 220 DIGITAL POSITIONER 42 18 85 EN REV E 67 Notes...