TZIDC-200, TZIDC-210, TZIDC-220
DIGITAL POSITIONER | 42/18-85-EN REV. E
43
Operating button functions
Control button
Meaning
ENTER
•
Acknowledge
message
• Start
an
action
• Save in the non-volatile memory
MODE
• Choose operating mode (operating level)
• Select parameter group or parameter
(configuration level)
UP
direction
button
DOWN
direction
button
Press and hold all four
buttons for 5 s
Reset
Menu levels
The positioner has two operating levels.
Operating level
On the operating level the positioner operates in one of four
possible operating modes (two for automatic control and
two for manual mode). Parameters cannot be changed or
saved on this level.
Configuration level
On this level most of the parameters of the positioner can be
changed locally. The PC is required to change the limit values
for the movement counter, the travel counter, and the user-
defined characteristic curve.
On the configuration level the active operating mode is
deactivated. The I/P module is in neutral position. The
control operation is inactive.
NOTICE
Property damage
During external configuration via a PC, the positioner no
longer responds to the set point current. This may lead to
process failures.
• Before any external parameterization, always move the
actuator to the safety position and activate manual
adjustment.
Change from two to one column
Содержание TZIDC-200
Страница 59: ...TZIDC 200 TZIDC 210 TZIDC 220 DIGITAL POSITIONER 42 18 85 EN REV E 59 FM installation drawing No 901176...
Страница 61: ...TZIDC 200 TZIDC 210 TZIDC 220 DIGITAL POSITIONER 42 18 85 EN REV E 61...
Страница 63: ...TZIDC 200 TZIDC 210 TZIDC 220 DIGITAL POSITIONER 42 18 85 EN REV E 63 FM installation drawing No 901265...
Страница 65: ...TZIDC 200 TZIDC 210 TZIDC 220 DIGITAL POSITIONER 42 18 85 EN REV E 65 Change from one to two columns...
Страница 67: ...TZIDC 200 TZIDC 210 TZIDC 220 DIGITAL POSITIONER 42 18 85 EN REV E 67 Notes...