TZIDC-200, TZIDC-210, TZIDC-220
DIGITAL POSITIONER | 42/18-85-EN REV. E
13
ATEX – ‘Ex i’ type of protection
Ex marking
Marking
II 2 G Ex ia IIC T6 or T4 Gb
II 2 G Ex ib IIC T6 or T4 Gb
II 3 G Ex ic IIC T6 or T4 Gc
Type Examination Test Certificate
TÜV 02 ATEX 1831 X
Type TZIDC-210
Standards EN
60079-0
EN 60079-11
Temperature Data
Device group II 2 G
Temperature class
Ambient temperature Ta
T4
−
40 to 85 °C
T5
−
40 to 50 °C
T6
*
−
40 to 40 °C*
* When using the plug
−
in module for ‘Digital Feedback’ in Temperature
Class T6, the maximum permissible ambient temperature range is
−
40 to 35 °C (
−
40 to 95 °F).
Electrical data for ia / ib / ic for groups IIB / IIC
With the intrinsically safe Ex i IIC type of ignition protection, only
for connection to a certified FISCO power supply unit or a
barrier, i.e., a power supply unit with maximum values according
to the following table:
Current circuit (terminal)
Electrical information (maximum values)
Signal circuit
(+11 /
−
12)
U
i
= 24 V
I
i
= 250 mA
P
i
= 1.2 W
C
i
< 5 nF
L
i
< 10
μ
H
Characteristic curve =
linear
With the intrinsically safe Ex i IIC type of protection, only for
connection to a certified intrinsically safe circuit with maximum
values:
Current circuit (terminal)
Electrical information (maximum values)
Mechanical digital feedback
(+51 /
−
52)
(+41 /
−
42)
For maximum values, see EC type examination
certificate number
PTB 00 ATEX 2049 X
Special conditions
• Before final installation, the operator needs to decide on the
use of the device, either
A) as a device with ‘Ex i’ intrinsically safe type of protection
or
B) as a device with ‘Ex d’ type of protection
and permanently mark the selected type of use on the name
plate. Specific conditions of the surrounding environment,
such as chemical corrosion, must be taken into account when
affixing the permanent mark. Only the manufacturer must
change the selected type of use following a re-examination
• Variants that, according to declarations, also meet the
requirements for the ‘flameproof enclosure’ type of
protection may no longer be used as ‘intrinsically safe’ if they
have been previously used as a flameproof type of protection
IECEx – ‘Ex d’ type of protection
Ex marking
Marking
Ex d IIC T4/T5/T6
Type Examination Test Certificate
IECEx BVS 07.0030X, Issue No.: 0
Type TZIDC-200
Standards IEC
60079-0
IEC 60079-1
Temperature Data
Temperature class
Ambient temperature Ta
T4
−
40 to 85 °C
T5
−
40 to 80 °C
T6
−
40 to 65 °C
Содержание TZIDC-200
Страница 59: ...TZIDC 200 TZIDC 210 TZIDC 220 DIGITAL POSITIONER 42 18 85 EN REV E 59 FM installation drawing No 901176...
Страница 61: ...TZIDC 200 TZIDC 210 TZIDC 220 DIGITAL POSITIONER 42 18 85 EN REV E 61...
Страница 63: ...TZIDC 200 TZIDC 210 TZIDC 220 DIGITAL POSITIONER 42 18 85 EN REV E 63 FM installation drawing No 901265...
Страница 65: ...TZIDC 200 TZIDC 210 TZIDC 220 DIGITAL POSITIONER 42 18 85 EN REV E 65 Change from one to two columns...
Страница 67: ...TZIDC 200 TZIDC 210 TZIDC 220 DIGITAL POSITIONER 42 18 85 EN REV E 67 Notes...