TZIDC-200, TZIDC-210, TZIDC-220
DIGITAL POSITIONER | 42/18-85-EN REV. E
37
Operating modes
Selection from the operating level
1. Press and hold down
MODE
.
2. Also press and release
rapidly as often as required. The
selected operating mode is displayed.
3. Release
MODE
.
The position is displayed in % or as a rotation angle.
Operating mode
Mode indicator
Position indicator
1.0
Control mode* with
adaptation of the control
parameters
1.1
Control mode* without
adaptation of the control
parameters
1.2
Manual adjustment** in
the operating range.
Adjust*** using
or
1.3
Manual adjustment** in
the measuring range.
Adjust*** using
or
* Since self-optimization in operating mode 1.0 is subject to several factors
during control operation with adaptation, incorrect adjustments could
appear over an extended period.
** Positioning not active.
*** For high-speed mode, press
and
simultaneously.
TZIDC-210, -220
Commissioning the positioner:
1. Open the pneumatic power supply.
2. Connect fieldbus or power supply to the bus connections.
The following is now shown in the display:
3.
Checking mechanical mounting:
• Press and hold down
MODE
and
ENTER
; once the
countdown has gone from 3 to 0, release
MODE
and
ENTER
. The device switches to the operating level n
operating mode 1.x.
• Press and hold
MODE
and
ENTER
, and then press
or
until operating mode 1.3 (manual adjustment within the
sensor range) is displayed. Release
MODE
.
• Press
or
to move the actuator into the mechanical
end position; check the end positions; rotation angle is
displayed in degrees; for high-speed mode, press
or
simultaneously.
Recommended rotational angle range
Linear actuators
−
28 to 28°
Rotary actuators
−
57 to 57°
Minimum angle
25°
4. Go back to the bus level:
• Press and hold down
MODE
and
ENTER
; once the
countdown has gone from 3 to 0, release
MODE
and
ENTER
.
The following is now shown in the display:
5. Perform standard automatic adjustment in accordance with
Standard automatic adjustment
on page 39. Make sure the
device is on the bus level (
REMOTE
).
6.
Set dead zone and tolerance band. This step is only required
for critical (e.g. very small) actuators. In normal cases you can
skip this step.
Commissioning of the positioner is now complete, and the
device is ready for operation.
Содержание TZIDC-200
Страница 59: ...TZIDC 200 TZIDC 210 TZIDC 220 DIGITAL POSITIONER 42 18 85 EN REV E 59 FM installation drawing No 901176...
Страница 61: ...TZIDC 200 TZIDC 210 TZIDC 220 DIGITAL POSITIONER 42 18 85 EN REV E 61...
Страница 63: ...TZIDC 200 TZIDC 210 TZIDC 220 DIGITAL POSITIONER 42 18 85 EN REV E 63 FM installation drawing No 901265...
Страница 65: ...TZIDC 200 TZIDC 210 TZIDC 220 DIGITAL POSITIONER 42 18 85 EN REV E 65 Change from one to two columns...
Страница 67: ...TZIDC 200 TZIDC 210 TZIDC 220 DIGITAL POSITIONER 42 18 85 EN REV E 67 Notes...