![ABB TZIDC-200 Скачать руководство пользователя страница 52](http://html1.mh-extra.com/html/abb/tzidc-200/tzidc-200_operating-instruction_3460595052.webp)
52
TZIDC-200, TZIDC-210, TZIDC-220
DIGITAL POSITIONER | 42/18-85-EN REV. E
… 11 Diagnosis / error messages
… TZIDC error codes
Error code
Possible cause
Impact
Troubleshooting the Instrument
Error while processing the measured
values, pointing to an error in the working
data (RAM).
The actuator is moved to the safe position.
After approx. 5 seconds, the positioner is
automatically reset and the RAM is
reinitialized.
If the error persists even after the positioner
has been reset, the device will need to be
returned to the manufacturer for repair.
Error during the table processing, pointing
to an error in the working data (RAM).
The actuator is moved to the safe position.
After approx. 5 seconds, the positioner is
automatically reset and the RAM is
reinitialized.
If the error persists even after the positioner
has been reset, the device will need to be
returned to the manufacturer for repair.
Error when verifying the checksum of the
configuration data (RAM).
The actuator is moved to the safe position.
After approx. 5 seconds, the positioner is
automatically reset and the RAM is
reinitialized.
If the error persists even after the positioner
has been reset, the device will need to be
returned to the manufacturer for repair.
Error in the processor function registers
(RAM).
The actuator is moved to the safe position.
After approx. 5 seconds, the positioner is
automatically reset and the RAM is
reinitialized.
If the error persists even after the positioner
has been reset, the device will need to be
returned to the manufacturer for repair.
Internal error.
The actuator is moved to the safe position.
After approx. 5 seconds, the positioner is
automatically reset.
If the error can be reproduced and occurs in
the same position after resetting, the device
must be returned for repair to the
manufacturer.
Содержание TZIDC-200
Страница 59: ...TZIDC 200 TZIDC 210 TZIDC 220 DIGITAL POSITIONER 42 18 85 EN REV E 59 FM installation drawing No 901176...
Страница 61: ...TZIDC 200 TZIDC 210 TZIDC 220 DIGITAL POSITIONER 42 18 85 EN REV E 61...
Страница 63: ...TZIDC 200 TZIDC 210 TZIDC 220 DIGITAL POSITIONER 42 18 85 EN REV E 63 FM installation drawing No 901265...
Страница 65: ...TZIDC 200 TZIDC 210 TZIDC 220 DIGITAL POSITIONER 42 18 85 EN REV E 65 Change from one to two columns...
Страница 67: ...TZIDC 200 TZIDC 210 TZIDC 220 DIGITAL POSITIONER 42 18 85 EN REV E 67 Notes...