![ABB RET615 Скачать руководство пользователя страница 94](http://html.mh-extra.com/html/abb/ret615/ret615_manual_2840094.webp)
0xA
CS
IEC 61850 name
SA name
Description
Values
2133
6.05
.SPCS06.ctlVal
Output 6 control
0/1=Off/On
2134
6.06
.SPCS07.ctlVal
Output 7 control
0/1=Off/On
2135
6.07
.SPCS08.ctlVal
Output 8 control
0/1=Off/On
2136
6.08
.SPCS09.ctlVal
Output 9 control
0/1=Off/On
2137
6.09
.SPCS10.ctlVal
Output 10 control
0/1=Off/On
2138
6.10
.SPCS11.ctlVal
Output 11 control
0/1=Off/On
2139
6.11
.SPCS12.ctlVal
Output 12 control
0/1=Off/On
2140
6.12
.SPCS13.ctlVal
Output 13 control
0/1=Off/On
2141
6.13
.SPCS14.ctlVal
Output 14 control
0/1=Off/On
2142
6.14
.SPCS15.ctlVal
Output 15 control
0/1=Off/On
2143
6.15
.SPCS16.ctlVal
Output 16 control
0/1=Off/On
2.5.9
LD0.SRGAPC1 Set-reset (8 pcs) (1)
Table 173:
LD0.SRGAPC1 Set-reset (8 pcs) (1)
0xA
CS
IEC 61850 name
SA name
Description
Values
LD0.SRGAPC1
2096
4.00
.Rs1.Oper.ctlVal
Reset flip-flop 1
1=Reset
2097
4.01
.Rs2.Oper.ctlVal
Reset flip-flop 2
1=Reset
2098
4.02
.Rs3.Oper.ctlVal
Reset flip-flop 3
1=Reset
2099
4.03
.Rs4.Oper.ctlVal
Reset flip-flop 4
1=Reset
2100
4.04
.Rs5.Oper.ctlVal
Reset flip-flop 5
1=Reset
2101
4.05
.Rs6.Oper.ctlVal
Reset flip-flop 6
1=Reset
2102
4.06
.Rs7.Oper.ctlVal
Reset flip-flop 7
1=Reset
2103
4.07
.Rs8.Oper.ctlVal
Reset flip-flop 8
1=Reset
2.5.10
LD0.SRGAPC2 Set-reset (8 pcs) (2)
Table 174:
LD0.SRGAPC2 Set-reset (8 pcs) (2)
0xA
CS
IEC 61850 name
SA name
Description
Values
LD0.SRGAPC2
2104
4.08
.Rs1.Oper.ctlVal
Reset flip-flop 1
1=Reset
2105
4.09
.Rs2.Oper.ctlVal
Reset flip-flop 2
1=Reset
2106
4.10
.Rs3.Oper.ctlVal
Reset flip-flop 3
1=Reset
2107
4.11
.Rs4.Oper.ctlVal
Reset flip-flop 4
1=Reset
2108
4.12
.Rs5.Oper.ctlVal
Reset flip-flop 5
1=Reset
2109
4.13
.Rs6.Oper.ctlVal
Reset flip-flop 6
1=Reset
2110
4.14
.Rs7.Oper.ctlVal
Reset flip-flop 7
1=Reset
2111
4.15
.Rs8.Oper.ctlVal
Reset flip-flop 8
1=Reset
Section 2
1MRS756878 H
Modbus data mappings
88