BitA
RegA
IEC 61850 name
SA name
Description
Values
3474
217.02
.Pos.stVal.Fault
-
Fault bit
1=Pos(00/11)
3475
217.03
.Pos.stSeld
-
Control selected
1=Selected
CTRL.DCCILO1
3476
217.04
.EnaOpn.stVal
ENA_OPEN
Open enabled
1=Enabled
3477
217.05
.EnaCls.stVal
ENA_CLOSE
Close enabled
1=Enabled
CTRL.DCXSWI1
3478
217.06
.BlkOpn.stVal
BLK_OPEN
Open blocked
1=Blocked
3479
217.07
.mcd
3480
217.08
.BlkCls.stVal
BLK_CLOSE
Close blocked
1=Blocked
3481
217.09
.mcd
CTRL.DCCILO1
3482
217.10
.ItlByps.stVal
ITL_BYPASS
Interlock bypass
1=Bypass
3483
217.11
.mcd
2.3.1.10
CTRL.DCXSWI2 Disconnector control (2)
Table 13:
CTRL.DCXSWI2 Disconnector control (2)
BitA
RegA
IEC 61850 name
SA name
Description
Values
CTRL.DCXSWI2
POSITION
3484
217.12
.Pos.stVal.Close
-
Close bit
1=Close
3485
217.13
.Pos.stVal.Open
-
Open bit
1=Open
3486
217.14
.Pos.stVal.Fault
-
Fault bit
1=Pos(00/11)
3487
217.15
.Pos.stSeld
-
Control selected
1=Selected
CTRL.DCCILO2
3488
218.00
.EnaOpn.stVal
ENA_OPEN
Open enabled
1=Enabled
3489
218.01
.EnaCls.stVal
ENA_CLOSE
Close enabled
1=Enabled
CTRL.DCXSWI2
3490
218.02
.BlkOpn.stVal
BLK_OPEN
Open blocked
1=Blocked
3491
218.03
.mcd
3492
218.04
.BlkCls.stVal
BLK_CLOSE
Close blocked
1=Blocked
3493
218.05
.mcd
CTRL.DCCILO2
3494
218.06
.ItlByps.stVal
ITL_BYPASS
Interlock bypass
1=Bypass
3495
218.07
.mcd
Section 2
1MRS756878 H
Modbus data mappings
20
RET615
Point List Manual