![ABB RET615 Скачать руководство пользователя страница 91](http://html.mh-extra.com/html/abb/ret615/ret615_manual_2840091.webp)
0xA
CS
IEC 61850 name
SA name
Description
Values
2068
2.08
.MemClr.Oper.ctlVal
Clear DR memory
1=Clear
LD0.CMMXU1
2069
2.09
.RecRs.Oper.ctlVal
Reset max current1 demands
1=Reset
LD0.PEMMXU1
2070
2.10
.SupDmdRs.Oper.ctlVal
Reset energy values
1=Reset
LD0.SCCBR1
2071
2.11
.RsTrvTm.Oper.ctlVal
Reset CB travel time
1=Reset
2072
2.12
.RsSprChaTm.Oper.ctlV
al
Reset CB spring charge time
1=Reset
LD0.RESCMMXU1
2073
2.13
.RecRs.Oper.ctlVal
Reset Io (1) max demands
1=Reset
LD0.RESVMMXU1
2074
2.14
.RecRs.Oper.ctlVal
Reset Uo (1) max demands
1=Reset
LD0.CMMXU2
2075
2.15
.RecRs.Oper.ctlVal
Reset max current2 demands
1=Reset
LD0.RESCMMXU2
2076
3.14
.RecRs.Oper.ctlVal
Reset Io (2) max demands
1=Reset
2.5.2
CTRL.CBCSWI1 Circuit breaker control (1)
Table 166:
CTRL.CBCSWI1 Circuit breaker control (1)
0xA
CS
IEC 61850 name
SA name
Description
Values
CTRL.CBCSWI1
2048
1.00
.Pos.Oper.ctlVal
Select open
1=Select
2049
1.01
.Pos.Oper.ctlVal
Select close
1=Select
2050
1.02
.Pos.Oper.ctlVal
Cancel selection
1=Cancel
2051
1.03
.Pos.Oper.ctlVal
Execute selection
1=Execute
2052
1.04
.Pos.Oper.ctlVal
Direct open
1=Open
2053
1.05
.Pos.Oper.ctlVal
Direct close
1=Close
2.5.3
CTRL.DCXSWI1 Disconnector control (1)
Table 167:
CTRL.DCXSWI1 Disconnector control (1)
0xA
CS
IEC 61850 name
SA name
Description
Values
CTRL.DCCSWI1
2144
7.00
.Pos.Oper.ctlVal
Select open
1=Select
2145
7.01
.Pos.Oper.ctlVal
Select close
1=Select
2146
7.02
.Pos.Oper.ctlVal
Cancel selection
1=Cancel
Table continues on next page
1MRS756878 H
Section 2
Modbus data mappings
RET615
85
Point List Manual