![ABB RET615 Скачать руководство пользователя страница 76](http://html.mh-extra.com/html/abb/ret615/ret615_manual_2840076.webp)
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
2066
u16
1
.WacTrg.stVal
Num. of watchdog resets
0...65535
2067
u16
1
.NumCmpChg.stVal
Num. of conf. changes
0...65535
LD0.LLN0
u16
1
.ParChgCnt.stVal
Num. of setting changes
0…65535
1) See the technical manual.
2.4.1.24
Time and reason for latest protection relay reset
Table 127:
Time and reason for latest protection relay reset
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
9221
u16
1
Year
2000...2999
9222
u16
1
Month
1...12
9223
u16
1
Day
1...31
9224
u16
1
Hour
0...23
9225
u16
1
Minute
0...59
9226
u16
1
Second
0...59
9227
u16
1
Millisecond
0…999
9228
u16
1
Reset reason
9228.0
Bit
- bit 0
1=Cold start
9228.1
Bit
- bit 1
1=Watchdog
9228.2
Bit
- bit 2
1=Warm start
2.4.1.25
User-definable bits [Alt.2], visible on 0x,1x,3x and 4x
Table 128:
User-definable bits [Alt.2], visible on 0x,1x,3x and 4x
BitA
Type
Scale
IEC 61850 name
SA name
Description
Values
(0)
Bit
< not mappable - not visible >
1
Bit
Usr reg 1.Bit 01
2
Bit
Usr reg 1.Bit 02
3
Bit
Usr reg 1.Bit 03
:
:
:
:
:
:
15
Bit
Usr reg 1.Bit 15
16
Bit
Usr reg 2.Bit 00
17
Bit
Usr reg 2.Bit 01
:
:
:
:
:
:
2046
Bit
Usr reg 127.Bit 14
2047
Bit
Usr reg 127.Bit 15
Section 2
1MRS756878 H
Modbus data mappings
70
RET615
Point List Manual