![ABB RET615 Скачать руководство пользователя страница 92](http://html.mh-extra.com/html/abb/ret615/ret615_manual_2840092.webp)
0xA
CS
IEC 61850 name
SA name
Description
Values
2147
7.03
.Pos.Oper.ctlVal
Execute selection
1=Execute
2148
7.04
.Pos.Oper.ctlVal
Direct open
1=Open
2149
7.05
.Pos.Oper.ctlVal
Direct close
1=Close
2.5.4
CTRL.DCXSWI2 Disconnector control (2)
Table 168:
CTRL.DCXSWI2 Disconnector control (2)
0xA
CS
IEC 61850 name
SA name
Description
Values
CTRL.DCCSWI2
2150
7.06
.Pos.Oper.ctlVal
Select open
1=Select
2151
7.07
.Pos.Oper.ctlVal
Select close
1=Select
2152
7.08
.Pos.Oper.ctlVal
Cancel selection
1=Cancel
2153
7.09
.Pos.Oper.ctlVal
Execute selection
1=Execute
2154
7.10
.Pos.Oper.ctlVal
Direct open
1=Open
2155
7.11
.Pos.Oper.ctlVal
Direct close
1=Close
2.5.5
CTRL.ESXSWI1 Earthing switch control (1)
Table 169:
CTRL.ESXSWI1 Earthing switch control (1)
0xA
CS
IEC 61850 name
SA name
Description
Values
CTRL.ESXSWI1
2054
1.06
.Pos.Oper.ctlVal
Select open
1=Select
2055
1.07
.Pos.Oper.ctlVal
Select close
1=Select
2056
1.08
.Pos.Oper.ctlVal
Cancel selection
1=Cancel
2057
1.09
.Pos.Oper.ctlVal
Execute selection
1=Execute
2058
1.10
.Pos.Oper.ctlVal
Direct open
1=Open
2059
1.11
.Pos.Oper.ctlVal
Direct close
1=Close
2.5.6
LD0.LDEV1 Protection relay's warm reset (1)
Table 170:
LD0.LDEV1 Protection relay's warm reset (1)
0xA
CS
IEC 61850 name
SA name
Description
Values
LD0.LDEV1
2080
3.00
.WrmStrCmd.Oper.ctlVal
Warm reboot of protection relay 1=Reboot
Section 2
1MRS756878 H
Modbus data mappings
86
RET615