![ABB RET615 Скачать руководство пользователя страница 16](http://html.mh-extra.com/html/abb/ret615/ret615_manual_2840016.webp)
•
Abbreviations and acronyms are spelled out in the glossary. The glossary also
contains definitions of important terms.
•
Push button navigation in the LHMI menu structure is presented by using the
push button icons.
To navigate between the options, use
and
.
•
Menu paths are presented in bold.
Select
Main menu/Settings
.
•
LHMI messages are shown in Courier font.
To save the changes in nonvolatile memory, select
Yes
and press
.
•
Parameter names are shown in italics.
The function can be enabled and disabled with the
Operation
setting.
•
Parameter values are indicated with quotation marks.
The corresponding parameter values are "On" and "Off".
•
Input/output messages and monitored data names are shown in Courier font.
When the function starts, the
START
output is set to TRUE.
•
This document assumes that the parameter setting visibility is "Advanced".
1.4.3
Functions, codes and symbols
Table 1:
Functions included in the relay
Function
IEC 61850
IEC 60617
IEC-ANSI
Protection
Three-phase non-directional
overcurrent protection, low stage
PHLPTOC1
3I> (1)
51P-1 (1)
PHLPTOC2
3I> (2)
51P-1 (2)
Three-phase non-directional
overcurrent protection, high stage
PHHPTOC1
3I>> (1)
51P-2 (1)
PHHPTOC2
3I>> (2)
51P-2 (2)
Three-phase non-directional
overcurrent protection, instantaneous
stage
PHIPTOC1
3I>>> (1)
50P/51P (1)
PHIPTOC2
3I>>> (2)
50P/51P (2)
Non-directional earth-fault protection,
low stage
EFLPTOC1
Io> (1)
51N-1 (1)
EFLPTOC2
Io> (2)
51N-1 (2)
Non-directional earth-fault protection,
high stage
EFHPTOC1
Io>> (1)
51N-2 (1)
EFHPTOC2
Io>> (2)
51N-2 (2)
Negative-sequence overcurrent
protection
NSPTOC1
I2> (1)
46 (1)
NSPTOC2
I2> (2)
46 (2)
Residual overvoltage protection
ROVPTOV1
Uo> (1)
59G (1)
ROVPTOV2
Uo> (2)
59G (2)
Three-phase undervoltage protection PHPTUV1
3U< (1)
27 (1)
PHPTUV2
3U< (2)
27 (2)
Three-phase overvoltage protection
PHPTOV1
3U> (1)
59 (1)
PHPTOV2
3U> (2)
59 (2)
Three-phase thermal overload
protection, two time constants
T2PTTR1
3Ith>T/G/C (1)
49T/G/C (1)
Table continues on next page
Section 1
1MRS756878 H
Introduction
10
RET615
Point List Manual