![ABB RET615 Скачать руководство пользователя страница 69](http://html.mh-extra.com/html/abb/ret615/ret615_manual_2840069.webp)
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
9434
u16
1000
.DifARes.mag
Diff. current Io
0.000...80.00
0 [pu]
9435
u16
1000
.RstARes.mag
Bias current Io
0.000…
50.000 [pu]
9436
u16
1000
.Max50APhsA1.mag
Max. current phs A(1)
0.000…
50.000 [×In]
9437
u16
1000
.Max50APhsB1.mag
Max. current phs B(1)
0.000…
50.000 [×In]
9438
u16
1000
.Max50APhsC1.mag
Max. current phs C(1)
0.000…
50.000 [×In]
9439
u16
1000
.Max50ARes1.mag
Max. current Io(1)
0.000…
50.000 [×In]
9440
u16
1000
.APhsA1.mag
Current phs A(1)
0.000…
50.000 [×In]
9441
u16
1000
.APhsB1.mag
Current phs B(1)
0.000…
50.000 [×In]
9442
u16
1000
.APhsC1.mag
Current phs C(1)
0.000…
50.000 [×In]
9443
u16
1000
.ARes1.mag
Current Io(1)
0.000…
50.000 [×In]
9444
u16
1000
.AResClc1.mag
Current Io-Calc(1)
0.000…
50.000 [×In]
9445
u16
1000
.APsSeq1.mag
Current Ps-Seq(1)
0.000…
50.000 [×In]
9446
u16
1000
.ANgSeq1.mag
Current Ng-Seq(1)
0.000…
50.000 [×In]
9447
u16
1000
.PhVPhsA1.mag
Voltage phs A(1)
0.000...4.000
[×Un]
9448
u16
1000
.PhVPhsB1.mag
Voltage phs B(1)
0.000...4.000
[×Un]
9449
u16
1000
.PhVPhsC1.mag
Voltage phs C(1)
0.000...4.000
[×Un]
9450
u16
1000
.PPVPhsAB1.mag
Voltage phs AB(1)
0.000...4.000
[×Un]
9451
u16
1000
.PPVPhsBC1.mag
Voltage phs BC(1)
0.000...4.000
[×Un]
9452
u16
1000
.PPVPhsCA1.mag
Voltage phs CA(1)
0.000...4.000
[×Un]
9453
u16
1000
.VRes1.mag
Voltage Uo(1)
0.000...4.000
[×Un]
9454
u16
1000
.VZro1.mag
Voltage Zro-Seq(1)
0.000...4.000
[×Un]
9455
u16
1000
.VPsSeq1.mag
Voltage Ps-Seq(1)
0.000...4.000
[×Un]
9456
u16
1000
.VNgSeq1.mag
Voltage Ng-Seq(1)
0.000...4.000
[×Un]
9457
u16
100
.MaxTmpRl.mag
PTTR thermal level
0.00...99.99
9458
u16
100
.AMaxNgPs.mag
PDNSPTOC1 ratio I2/I1
0.00...999.99
[%]
Table continues on next page
1MRS756878 H
Section 2
Modbus data mappings
RET615
63
Point List Manual