2.3.1.42
LD0.PHHPTOC1 Three-phase non-directional overcurrent protection,
high stage (1)
Table 45:
LD0.PHHPTOC1 Three-phase non-directional overcurrent protection, high stage (1)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.PHHPTOC1
2890
180.10
.Str.general
START
General start
1=Start
2891
180.11
.mcd
2892
180.12
.Str.phsA
Phs A start
1=Start
2893
180.13
.mcd
2894
180.14
.Str.phsB
Phs B start
1=Start
2895
180.15
.mcd
2896
181.00
.Str.phsC
Phs C start
1=Start
2897
181.01
.mcd
2898
181.02
.Op.general
OPERATE
General operate
1=Operate
2899
181.03
.mcd
2.3.1.43
LD0.PHHPTOC2 Three-phase non-directional overcurrent protection,
high stage (2)
Table 46:
Three-phase non-directional overcurrent protection, high stage (2)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.PHHPTOC2
2920
182.08
.Str.general
START
General start
1=Start
2921
182.09
.mcd
2922
182.10
.Str.phsA
phsA start
1=Start
2923
182.11
.mcd
2924
182.12
.Str.phsB
phsB start
1=Start
2925
182.13
.mcd
2926
182.14
.Str.phsC
phsC start
1=Start
2927
182.15
.mcd
2928
183.00
.Op.general
OPERATE
General operate
1=Operate
2929
183.01
.mcd
Section 2
1MRS756878 H
Modbus data mappings
32
RET615
Point List Manual