![ABB RET615 Скачать руководство пользователя страница 78](http://html.mh-extra.com/html/abb/ret615/ret615_manual_2840078.webp)
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
2004
Year - month
2005
Day - hour
2006
Minute - second
2007
Milliseconds
2008
Time quality
LD0.CMAMMXU1
Max demand values
2009
u16
1000
.A.phsA.cVal.mag
Max demand IL1
Phs A amplitude
0.00…50.0
[xIn]
2010
Year - month
2011
Day - hour
2012
Minute - second
2013
Milliseconds
2014
Time quality
2015
u16
1000
.A.phsB.cVal.mag
Max demand IL2
Phs B amplitude
0.00…50.0
[xIn]
2016
Year - month
2017
Day - hour
2018
Minute - second
2019
Milliseconds
2020
Time quality
2021
u16
1000
.A.phsC.cVal.mag
Max demand IL2
Phs C amplitude
0.00…50.0
[xIn]
2022
Year - month
2023
Day - hour
2024
Minute - second
2025
Milliseconds
2026
Time quality
LD0.CMIMMXU1
Min demand values
u16
1000
.A.phsA.cVal.mag
Max demand IL1
Phs A amplitude
0.00…50.0
[xIn]
u16
1000
.A.phsB.cVal.mag
Max demand IL2
Phs B amplitude
0.00…50.0
[xIn]
u16
1000
.A.phsC.cVal.mag
Max demand IL3
Phs C amplitude
0.00…50.0
[xIn]
Section 2
1MRS756878 H
Modbus data mappings
72
RET615
Point List Manual