![ABB RET615 Скачать руководство пользователя страница 80](http://html.mh-extra.com/html/abb/ret615/ret615_manual_2840080.webp)
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
2044
u16
-
Minute - second
2045
u16
-
Milliseconds
2046
u16
-
Time quality
2047
u16
1000
.MaxAmpsC.mag
Max demand IL3
Max. phsC demand
0.00...40.0
[xIn]
Update time stamp
see doc.
2048
u16
-
Year - month
2049
u16
-
Day - hour
2050
u16
-
Minute - second
2051
u16
-
Milliseconds
2052
u16
-
Time quality
2.4.1.32
LD0.CMMXU2 Three-phase current measurement (2)
Table 135:
LD0.CMMXU2 Three-phase current measurement (2)
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
LD0.CMMXU2
Phase current (2)
152
u16
1000
.A.phsA.instCVal.mag
I_INST_A
Phs A amplitude
0.00...40.0
[xIn]
153
u16
1000
.A.phsB.instCVal.mag
I_INST_B
Phs B amplitude
0.00...40.0
[xIn]
154
u16
1000
.A.phsC.instCVal.mag
I_INST_C
Phs C amplitude
0.00...40.0
[xIn]
2.4.1.33
LD0.CSMSQI1 Sequence current measurement (1)
Table 136:
LD0.CSMSQI1 Sequence current measurement (1)
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
LD0.CSMSQI1
Sequence of currents
142
u16
1000
.SeqA.c1.instCVal.mag
I1_INST
Positive amplitude
0.00...40.0
[xIn]
143
u16
1000
.SeqA.c2.instCVal.mag
I2_INST
Negative amplitude
0.00...40.0
[xIn]
144
u16
1000
.SeqA.c2.instCVal.mag
I3_INST
Zero amplitude
0.00...40.0
[xIn]
Section 2
1MRS756878 H
Modbus data mappings
74
RET615