little meaning, since it is always possible to redefine the settings completely for the
user-definable register.
2.4.2.1
CTRL.LLN0 Local, Remote, Station, Off and Combinations
Table 155:
CTRL.LLN0 Local, Remote, Station, Off and Combinations
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
CTRL.LLN0
u16
1
.LocKeyHMI.stVal
0=Off; 1=Loc; 2=Rem; 3=Stat;
4=L+R; 5=L+S; 6=L+S+R; 7=S
+R
0…7
2.4.2.2
LD0.FMMXU1 Frequency measurement (1)
Table 156:
LD0.FMMXU1 Frequency measurement (1)
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
LD0.FMMXU1
u16
100
.Hz.mag
F_DB
Frequency
35.00...75.00
[Hz]
2.4.2.3
LD0.LLN0/LPHD1/LDEV1 System values
Table 157:
LD0.LLN0/LPHD1/LDEV1 System values
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
LD0.LLN0
u16
1
.ParChgCnt.stVal
Num. of setting changes
0…65535
2.4.2.4
LD0.MDSOPT1 Runtime counter for machines and devices (1)
Table 158:
LD0.MDSOPT1 Runtime counter for machines and devices (1)
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
LD0.MDSOPT1
u16
1
.OpTmh.stVal
OPR_TIME
Total operation hours
0…299999
2.4.2.5
LD0.MVI4GAPC1 Integer value move (1)
Table 159:
LD0.MVI4GAPC1 Integer value move (1)
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
LD0.MVI4GAPC1
i32
1
.ISCS01.stVal
OUT1
- Integer value 1 (high)
-/
+2147483647
- Low word
Table continues on next page
Section 2
1MRS756878 H
Modbus data mappings
82
RET615
Point List Manual