RELION® 615 SERIES

Transformer Protection and Control

RET615

Modbus Point List Manual

Содержание RET615

Страница 1: ... RELION 615 SERIES Transformer Protection and Control RET615 Modbus Point List Manual ...

Страница 2: ......

Страница 3: ...Document ID 1MRS756878 Issued 2018 12 20 Revision H Product version 5 0 FP1 Copyright 2018 ABB All rights reserved ...

Страница 4: ...ibed in this document is furnished under a license and may be used copied or disclosed only in accordance with the terms of such license Trademarks ABB and Relion are registered trademarks of the ABB Group All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders Warranty Please inquire about the terms of warranty from your n...

Страница 5: ...cted and communicate data and information via a network interface which should be connected to a secure network It is the sole responsibility of the person or entity responsible for network administration to ensure a secure connection to the network and to take the necessary measures such as but not limited to installation of firewalls application of authentication measures encryption of data inst...

Страница 6: ...nd concerning electrical equipment for use within specified voltage limits Low voltage directive 2006 95 EC This conformity is the result of tests conducted by ABB in accordance with the product standard EN 60255 26 for the EMC directive and with the product standards EN 60255 1 and EN 60255 27 for the low voltage directive The product is designed in accordance with the international standards of ...

Страница 7: ...mom mcd position 18 CTRL CBXCBR1 Circuit breaker control 1 18 CTRL DCSXSWI1 Disconnector position indication 1 19 CTRL DCSXSWI2 Disconnector position indication 2 19 CTRL DCSXSWI3 Disconnector position indication 3 19 CTRL DCXSWI1 Disconnector control 1 19 CTRL DCXSWI2 Disconnector control 2 20 CTRL ESSXSWI1 Earthing switch indication 1 21 CTRL ESSXSWI2 Earthing switch indication 2 21 CTRL ESXSWI1...

Страница 8: ...ose protection 4 29 LD0 MAPGAPC5 Multipurpose protection 5 29 LD0 MAPGAPC6 Multipurpose protection 6 29 LD0 MDSOPT1 Runtime counter for machines and devices 1 30 LD0 MVGAPC1 Move 8 pcs 1 30 LD0 MVGAPC2 Move 8 pcs 2 30 LD0 NSPTOC1 Negative sequence overcurrent protection 1 31 LD0 NSPTOC2 Negative sequence overcurrent protection 2 31 LD0 PHHPTOC1 Three phase non directional overcurrent protection hi...

Страница 9: ...sical I O states AIM card XA130 42 LD0 XARGGIO130 Alarm warning 42 LD0 XBGGIO110 Physical I O states BIO card XB110 42 LD0 XGGIO100 Physical I O states PSM card X100 43 LD0 XGGIO110 Physical I O states BIO card X110 44 LD0 XGGIO130 Physical I O states BIO card X130 45 LD0 XRGGIO130 Alarm warning 46 Unmapped indications 46 All premapped three phase protection function stages operate phase dependent...

Страница 10: ...57 Fault record structure header 61 Fault record data 61 Protection relay s real time clock in local time mode read and write synchronize 65 Protection relay s real time clock in UTC time mode read and write synchronize 65 Indication bits mirrored in registers 66 SSR1 System status register 1 device health 66 SSR2 System status register 2 protection relay s mode and state 67 SSR3 System status reg...

Страница 11: ...ase thermal overload protection two time constants 2 79 LD0 TPOSYLTC1 Tap changer position indication 1 79 LD0 TR2PTDF1 Stabilized and instantaneous differential protection for two winding transformers 1 79 LD0 VMMXU1 Three phase voltage measurement 1 80 LD0 VMMXU1 Voltage demand values 1 80 LD0 VSMSQI1 Sequence voltage measurement 1 81 LD0 XARGGIO130 RTD input values 81 LD0 XRGGIO130 RTD input va...

Страница 12: ...s warm reset 1 86 LD0 SPCGAPC1 Generic control point 16 pcs 1 87 LD0 SPCGAPC2 Generic control point 16 pcs 2 87 LD0 SRGAPC1 Set reset 8 pcs 1 88 LD0 SRGAPC2 Set reset 8 pcs 2 88 Unmapped control points 89 Section 3 Glossary 91 Table of contents 6 RET615 Point List Manual ...

Страница 13: ...d audience This manual addresses the communication system engineer or system integrator responsible for pre engineering and engineering for communication setup in a substation from an protection relay perspective The system engineer or system integrator must have a basic knowledge of communication in protection and control systems and thorough knowledge of the specific communication protocol 1MRS7...

Страница 14: ...DF 8734 0C8B7116124C V2 EN Figure 1 The intended use of documents during the product life cycle Product series and product specific manuals can be downloaded from the ABB Web site http www abb com relion 1 3 2 Document revision history Document revision date Product version History A 2009 07 03 2 0 First release B 2010 06 11 3 0 Content updated to correspond to the product version C 2012 05 11 4 0...

Страница 15: ...t indicate the presence of a hazard which could result in corruption of software or damage to equipment or property The information icon alerts the reader of important facts and conditions The tip icon indicates advice on for example how to design your project or how to use a certain function Although warning hazards are related to personal injury it is necessary to understand that under certain o...

Страница 16: ...ctions included in the relay Function IEC 61850 IEC 60617 IEC ANSI Protection Three phase non directional overcurrent protection low stage PHLPTOC1 3I 1 51P 1 1 PHLPTOC2 3I 2 51P 1 2 Three phase non directional overcurrent protection high stage PHHPTOC1 3I 1 51P 2 1 PHHPTOC2 3I 2 51P 2 2 Three phase non directional overcurrent protection instantaneous stage PHIPTOC1 3I 1 50P 51P 1 PHIPTOC2 3I 2 50...

Страница 17: ... ARC 1 50L 50NL 1 ARCSARC2 ARC 2 50L 50NL 2 ARCSARC3 ARC 3 50L 50NL 3 Multipurpose protection MAPGAPC1 MAP 1 MAP 1 MAPGAPC2 MAP 2 MAP 2 MAPGAPC3 MAP 3 MAP 3 MAPGAPC4 MAP 4 MAP 4 MAPGAPC5 MAP 5 MAP 5 MAPGAPC6 MAP 6 MAP 6 MAPGAPC7 MAP 7 MAP 7 MAPGAPC8 MAP 8 MAP 8 MAPGAPC9 MAP 9 MAP 9 MAPGAPC10 MAP 10 MAP 10 MAPGAPC11 MAP 11 MAP 11 MAPGAPC12 MAP 12 MAP 12 MAPGAPC13 MAP 13 MAP 13 MAPGAPC14 MAP 14 MAP ...

Страница 18: ...MMXU1 3I 1 3I 1 CMMXU2 3I 2 3I 2 Sequence current measurement CSMSQI1 I1 I2 I0 1 I1 I2 I0 1 Residual current measurement RESCMMXU1 Io 1 In 1 RESCMMXU2 Io 2 In 2 Three phase voltage measurement VMMXU1 3U 1 3V 1 Residual voltage measurement RESVMMXU1 Uo 1 Vn 1 Sequence voltage measurement VSMSQI1 U1 U2 U0 1 V1 V2 V0 1 Three phase power and energy measurement PEMMXU1 P E 1 P E 1 RTD mA measurement XR...

Страница 19: ...PC3 TON 3 TON 3 TONGAPC4 TON 4 TON 4 Set reset 8 pcs SRGAPC1 SR 1 SR 1 SRGAPC2 SR 2 SR 2 SRGAPC3 SR 3 SR 3 SRGAPC4 SR 4 SR 4 Move 8 pcs MVGAPC1 MV 1 MV 1 MVGAPC2 MV 2 MV 2 Generic control point 16 pcs SPCGAPC1 SPC 1 SPC 1 SPCGAPC2 SPC 2 SPC 2 Analog value scaling SCA4GAPC1 SCA4 1 SCA4 1 SCA4GAPC2 SCA4 2 SCA4 2 SCA4GAPC3 SCA4 3 SCA4 3 SCA4GAPC4 SCA4 4 SCA4 4 Integer value move MVI4GAPC1 MVI4 1 MVI4...

Страница 20: ...14 ...

Страница 21: ...e PHHPTOC1 1 HV 1 HV 1 HV 1 HV 1 HV 1 HV 1 HV 1 HV PHHPTOC2 1 LV 1 LV 1 LV 1 LV 1 LV 1 LV 1 LV 1 LV Three phase non directional overcurrent protection instantaneous stage PHIPTOC1 1 HV 1 HV 1 HV 1 HV 1 HV 1 HV 1 HV 1 HV PHIPTOC2 1 LV 1 LV 1 LV 1 LV 1 LV 1 LV 1 LV 1 LV Non directional earth fault protection low stage EFLPTOC1 1 HV 1 HV 1 1 HV 1 HV 1 EFLPTOC2 1 LV 1 LV 2 1 LV 1 LV 2 Non directional ...

Страница 22: ...LRC 1 1 1 1 1 1 1 1 Fault record FLTRFRC 1 1 1 1 1 1 1 1 Three phase current measurement CMMXU1 1 HV 1 HV 1 HV 1 HV 1 HV 1 HV 1 HV 1 HV CMMXU2 1 LV 1 LV 1 LV 1 LV 1 LV 1 LV 1 LV 1 LV Sequence current measurement CSMSQI1 1 HV 1 HV 1 HV 1 HV 1 HV 1 HV 1 HV 1 HV Residual current measurement RESCMMXU1 1 HV 1 HV 1 HV 1 HV RESCMMXU2 1 LV 1 LV 1 LV 1 LV Three phase voltage measurement VMMXU 1 HV 1 HV 1 H...

Страница 23: ...h IEC 61850 9 2 7 Available only with COM0031 0037 2 3 Indications Table 3 Explanations of the indications table columns Column name Description BitA Default 0X and 1X bit address for the data RegA Default 3X and 4X register bit 00 15 address for the data IEC 61850 name Original IED data object identification Described in the IEC 61850 format as Logical Device Logical Node and thereafter Data Obje...

Страница 24: ...yps stVal ITL_BYPASS Interlock bypass 1 Bypass 2835 177 03 mcd 2 3 1 4 CTRL CBCSWI1 Circuit breaker 1 mom mcd position Table 7 CTRL CBCSWI1 Circuit breaker 1 mom mcd position BitA RegA IEC 61850 name SA name Description Values CTRL CBCSWI1 POSITION 2816 176 00 Pos stVal Close Close bit 1 Close 2817 176 01 mcd 2818 176 02 Pos stVal Open Open bit 1 Open 2819 176 03 mcd 2820 176 04 reserved 2821 176 ...

Страница 25: ...me SA name Description Values CTRL DCSXSWI2 POSITION 2795 174 11 Pos stVal Close Close bit 1 Close 2796 174 12 Pos stVal Open Open bit 1 Open 2797 174 13 Pos stVal Fault Fault bit 1 Pos 00 11 2 3 1 8 CTRL DCSXSWI3 Disconnector position indication 3 Table 11 CTRL DCSXSWI3 Disconnector position indication 3 BitA RegA IEC 61850 name SA name Description Values CTRL DCSXSWI3 POSITION 2798 174 14 Pos st...

Страница 26: ...control 2 Table 13 CTRL DCXSWI2 Disconnector control 2 BitA RegA IEC 61850 name SA name Description Values CTRL DCXSWI2 POSITION 3484 217 12 Pos stVal Close Close bit 1 Close 3485 217 13 Pos stVal Open Open bit 1 Open 3486 217 14 Pos stVal Fault Fault bit 1 Pos 00 11 3487 217 15 Pos stSeld Control selected 1 Selected CTRL DCCILO2 3488 218 00 EnaOpn stVal ENA_OPEN Open enabled 1 Enabled 3489 218 01...

Страница 27: ...1 Pos 00 11 2 3 1 13 CTRL ESXSWI1 Earthing switch control 1 Table 16 CTRL ESXSWI1 Earthing switch control 1 BitA RegA IEC 61850 name SA name Description Values CTRL ESXSWI1 POSITION 3496 218 08 Pos stVal Close Close bit 1 Close 3497 218 09 Pos stVal Open Open bit 1 Open 3498 218 10 Pos stVal Fault Fault bit 1 Pos 00 11 3499 218 11 Pos stSeld Control selected 1 Selected CTRL ESCILO1 3500 218 12 Ena...

Страница 28: ...21 2988 186 12 Op general OPERATE Stage operate 1 Operate 2989 186 13 mcd 2 3 1 16 LD0 ARCSARC3 Arc protection 3 Table 19 LD0 ARCSARC3 Arc protection 3 BitA RegA IEC 61850 name SA name Description Values LD0 ARCSARC31 2990 186 14 FADet stVal ARC_FLT_DET Arc detected 1 Detected 2991 186 15 mcd LD0 ARCPTRC31 2994 187 02 Op general OPERATE Stage operate 1 Operate 2995 187 03 mcd 2 3 1 17 LD0 CCBRBRF1...

Страница 29: ... stVal LOW_ALARM Low alarm 1 Alarm 2759 172 07 mcd 2 3 1 19 LD0 CMMXU2 Three phase current measurement 2 Table 22 LD0 CMMXU2 Three phase current measurement 2 BitA RegA IEC 61850 name SA name Description Values LD0 CMMXU2 2784 174 00 HiAlm stVal HIGH_ALARM High alarm 1 Alarm 2785 174 01 mcd 2786 174 02 HiWrn stVal HIGH_WARN High warning 1 Warning 2787 174 03 mcd 2788 174 04 LoWrn stVal LOW_WARN Lo...

Страница 30: ... 184 10 Op general OPERATE Stage operate 1 Operate 2955 184 11 mcd 2 3 1 23 LD0 EFLPTOC1 Non directional earth fault protection low stage 1 Table 26 LD0 EFLPTOC1 Non directional earth fault protection low stage 1 BitA RegA IEC 61850 name SA name Description Values LD0 EFLPTOC1 2940 183 12 Str general START Stage start 1 Start 2941 183 13 mcd 2942 183 14 Op general OPERATE Stage operate 1 Operate 2...

Страница 31: ...tween red and green colors The default color for ALARM is red and green for OK Colors can however be reconfigured with a setting parameter OK ALARM RESET LEDx Signal NOT GUID 2AE4D47A 2BBD 4422 A81C CF2EB7473379 V1 EN Figure 2 Signal wired to both OK and ALARM inputs inverted to the other If the OK and ALARM inputs are wired to separate indication signals the LED will have three legal states and c...

Страница 32: ...Color1 2 3528 220 08 LEDSt9 stVal LED 9 state 0 1 Color1 2 3529 220 09 LEDSt10 stVal LED 10 state 0 1 Color1 2 3530 220 10 LEDSt11 stVal LED 11 state 0 1 Color1 2 3531 220 11 reserved 0 2 3 1 27 LD0 LEDGGIO1 Indication LED states OFF ColorX These LED indication points interpret the case when an indication signal is wired to either the OK or ALARM input of the LED function block The default color f...

Страница 33: ... 1 Off Color 2779 173 11 reserved 0 2 3 1 28 LD0 LEDPTRC1 Global conditioning 1 Table 31 LD0 LEDPTRC1 Global conditioning 1 BitA RegA IEC 61850 name SA name Description Values LD0 LEDPTRC1 2736 171 00 Str general Global start 1 Start 2737 171 01 mcd 2738 171 02 Op general Global operate 1 Operate 2739 171 03 mcd 2 3 1 29 LD0 LEDPTRC1 Global conditioning phase information 1 Table 32 LD0 LEDPTRC1 Gl...

Страница 34: ...e 1 Operate 2967 185 07 mcd 2 3 1 31 LD0 MAPGAPC1 Multipurpose protection 1 Table 34 LD0 MAPGAPC1 Multipurpose protection 1 BitA RegA IEC 61850 name SA name Description Values LD0 MAPGAPC1 3016 188 08 Op general OPERATE Stage operate 1 Operate 3017 188 09 mcd 3018 188 10 Str general START Stage start 1 Start 3019 188 11 mcd 2 3 1 32 LD0 MAPGAPC2 Multipurpose protection 2 Table 35 LD0 MAPGAPC2 Mult...

Страница 35: ...030 189 06 Str general START Stage start 1 Start 3031 189 07 mcd 2 3 1 35 LD0 MAPGAPC5 Multipurpose protection 5 Table 38 LD0 MAPGAPC5 Multipurpose protection 5 BitA RegA IEC 61850 name SA name Description Values LD0 MAPGAPC5 3036 189 12 Op general OPERATE Stage operate 1 Operate 3037 189 13 mcd 3038 189 14 Str general START Stage start 1 Start 3039 189 15 mcd 2 3 1 36 LD0 MAPGAPC6 Multipurpose pr...

Страница 36: ...SO2 stVal Input 2 0 1 Off On 3539 221 03 mcd 3540 221 04 SPCSO3 stVal Input 3 0 1 Off On 3541 221 05 mcd 3542 221 06 SPCSO4 stVal Input 4 0 1 Off On 3543 221 07 mcd 3544 221 08 SPCSO5 stVal Input 5 0 1 Off On 3545 221 09 mcd 3546 221 10 SPCSO6 stVal Input 6 0 1 Off On 3547 221 11 mcd 3548 221 12 SPCSO7 stVal Input 7 0 1 Off On 3549 221 13 mcd 3550 221 14 SPCSO8 stVal Input 8 0 1 Off On 3551 221 15...

Страница 37: ... protection 1 Table 43 LD0 NSPTOC1 Negative sequence overcurrent protection 1 BitA RegA IEC 61850 name SA name Description Values LD0 NSPTOC1 2956 184 12 Str general START Stage start 1 Start 2957 184 13 mcd 2958 184 14 Op general OPERATE Stage operate 1 Operate 2959 184 15 mcd 2 3 1 41 LD0 NSPTOC2 Negative sequence overcurrent protection 2 Table 44 LD0 NSPTOC2 Negative sequence overcurrent protec...

Страница 38: ...2898 181 02 Op general OPERATE General operate 1 Operate 2899 181 03 mcd 2 3 1 43 LD0 PHHPTOC2 Three phase non directional overcurrent protection high stage 2 Table 46 Three phase non directional overcurrent protection high stage 2 BitA RegA IEC 61850 name SA name Description Values LD0 PHHPTOC2 2920 182 08 Str general START General start 1 Start 2921 182 09 mcd 2922 182 10 Str phsA phsA start 1 S...

Страница 39: ... 12 Op general OPERATE General operate 1 Operate 2909 181 13 mcd 2 3 1 45 LD0 PHIPTOC2 Three phase non directional overcurrent protection instantaneous stage 2 Table 48 LD0 PHIPTOC2 Three phase non directional overcurrent protection instantaneous stage 2 BitA RegA IEC 61850 name SA name Description Values LD0 PHIPTOC2 2930 183 02 Str general START General start 1 Start 2931 183 03 mcd 2932 183 04 ...

Страница 40: ...80 08 Op general OPERATE General operate 1 Operate 2889 180 09 mcd 2 3 1 47 LD0 PHLPTOC2 Three phase non directional overcurrent protection low stage 2 Table 50 LD0 PHLPTOC2 Three phase non directional overcurrent protection low stage 2 BitA RegA IEC 61850 name SA name Description Values LD0 PHLPTOC2 2910 181 14 Str general START General start 1 Start 2911 181 15 mcd 2912 182 00 Str phsA phsA star...

Страница 41: ...voltage protection 2 BitA RegA IEC 61850 name SA name Description Values LD0 PHPTOV2 3098 193 10 Str general START General start 1 Start 3099 193 11 mcd 3100 193 12 Str phsA Phs A start 1 Start 3101 193 13 mcd 3102 193 14 Str phsB Phs B start 1 Start 3103 193 15 mcd 3104 194 00 Str phsC Phs C start 1 Start 3105 194 01 mcd 3106 194 02 Op general OPERATE General operate 1 Operate 3107 194 03 mcd 2 3...

Страница 42: ...eneral start 1 Start 3149 196 13 mcd 3150 196 14 Str phsA Phs A start 1 Start 3151 196 15 mcd 3152 197 00 Str phsB Phs B start 1 Start 3153 197 01 mcd 3154 197 02 Str phsC Phs C start 1 Start 3155 197 03 mcd 3156 197 04 Op general OPERATE General operate 1 Operate 3157 197 05 mcd 2 3 1 52 LD0 RESCMMXU1 Residual current measurement 1 Table 55 LD0 RESCMMXU1 Residual current measurement 1 BitA RegA I...

Страница 43: ...10 HiWrn stVal HIGH_WARN High warning 1 Warning 3051 190 11 mcd 2 3 1 55 LD0 ROVPTOV1 Residual overvoltage protection 1 Table 58 LD0 ROVPTOV1 Residual overvoltage protection 1 BitA RegA IEC 61850 name SA name Description Values LD0 ROVPTOV1 3168 198 00 Str general START General start 1 Start 3169 198 01 mcd 3170 198 02 Op general OPERATE General operate 1 Operate 3171 198 03 mcd 2 3 1 56 LD0 ROVPT...

Страница 44: ...227 04 SPCS03 stVal Ouput state 3 0 1 Off On 3637 227 05 mcd 3638 227 06 SPCS04 stVal Ouput state 4 0 1 Off On 3639 227 07 mcd 3640 227 08 SPCS05 stVal Ouput state 5 0 1 Off On 3641 227 09 mcd 3642 227 10 SPCS06 stVal Ouput state 6 0 1 Off On 3643 227 11 mcd 3644 227 12 SPCS07 stVal Ouput state 7 0 1 Off On 3645 227 13 mcd 3646 227 14 SPCS08 stVal Ouput state 8 0 1 Off On 3647 227 15 mcd 3648 228 ...

Страница 45: ...tions alarm 1 Alarm 2852 178 04 OpCntLO stVal OPR_LO CB operations lockout 1 Lockout 2853 178 05 LonTmAlm stVal MON_ALM CB inactive alarm 1 Alarm LD0 SSIGM1 2854 178 06 InsAlm stVal PRES_ALM Low pressure alarm 1 Alarm 2855 178 07 InsBlk stVal PRES_LO Low pressure lockout 1 Lockout LD0 SSCBR1 2856 178 08 APwrAlm stVal IPOW_ALM Lyt alarm 1 Alarm 2857 178 09 APwrLO stVal IPOW_LO Lyt lockout 1 Lockout...

Страница 46: ...3 14 CircAlm stVal ALARM Supervision alarm 1 Alarm 2783 173 15 mcd 2 3 1 63 LD0 TR2PTDF1 Stabilized and instantaneous differential protection for two winding transformers 1 Table 66 LD0 TR2PTDF1 Stabilized and instantaneous differential protection for two winding transformers 1 BitA RegA IEC 61850 name SA name Description Values LD0 TR2PTDF1 3000 187 08 Op general OPERATE General operate 1 Operate...

Страница 47: ...p input signal 1 Operate 2745 171 09 mcd 2746 171 10 Tr general Trip output signal 1 Trip 2747 171 11 mcd 2 3 1 66 LD0 VMMXU1 Three phase voltage measurement 1 Table 69 LD0 VMMXU1 Three phase voltage measurement 1 BitA RegA IEC 61850 name SA name Description Values LD0 VMMXU1 3040 190 00 HiAlm stVal HIGH_ALARM High alarm 1 Alarm 3041 190 01 mcd 3042 190 02 HiWrn stVal HIGH_WARN High warning 1 Warn...

Страница 48: ...D0 XARGGIO130 Alarm warning Table 71 LD0 XARGGIO130 Alarm warning BitA RegA IEC 61850 name SA name Description Values LD0 XARGGIO130 3032 189 08 Alm stVal XRGGIO130 Alarm 1 Alarm 3033 189 09 mcd 3034 189 10 Wrn stVal XRGGIO130 Warning 1 Warning 3035 189 11 mcd 2 3 1 69 LD0 XBGGIO110 Physical I O states BIO card XB110 Table 72 LD0 XBGGIO110 Physical I O states BIO card XB110 BitA RegA IEC 61850 nam...

Страница 49: ... X110 Output 1 State 0 1 Off On 3233 202 01 mcd mom only Mom only alternative 3234 202 02 SPCSO2 stVal X110 Output 2 State 0 1 Off On 3235 202 03 mcd mom only Mom only alternative 3236 202 04 SPCSO3 stVal X110 Output 3 State 0 1 Off On 3237 202 05 mcd mom only Mom only alternative 2 3 1 70 LD0 XGGIO100 Physical I O states PSM card X100 Table 73 LD0 XGGIO100 Physical I O states PSM card X100 BitA R...

Страница 50: ...t 1 State 0 1 Off On 3217 201 01 mcd mom only Mom only alternative 3218 201 02 Ind2 stVal X110 Input 2 State 0 1 Off On 3219 201 03 mcd mom only Mom only alternative 3220 201 04 Ind3 stVal X110 Input 3 State 0 1 Off On 3221 201 05 mcd mom only Mom only alternative 3222 201 06 Ind4 stVal X110 Input 4 State 0 1 Off On 3223 201 07 mcd mom only Mom only alternative 3224 201 08 Ind5 stVal X110 Input 5 ...

Страница 51: ...0 BitA RegA IEC 61850 name SA name Description Values LD0 XGGIO130 3184 199 00 Ind1 stVal X130 Input 1 State 0 1 Off On 3185 199 01 mcd mom only Mom only alternative 3186 199 02 Ind2 stVal X130 Input 2 State 0 1 Off On 3187 199 03 mcd mom only Mom only alternative 3188 199 04 Ind3 stVal X130 Input 3 State 0 1 Off On 3189 199 05 mcd mom only Mom only alternative 3190 199 06 Ind4 stVal X130 Input 4 ...

Страница 52: ...Unmapped indications Unmapped indications are indication data that have no initial Modbus mapping locations but can be added to the user definable Modbus area using the Communication Management tool in PCM600 If Modbus events are enabled for these indication signals the event identification is the user definable area address 2 3 2 1 All premapped three phase protection function stages operate phas...

Страница 53: ... 0 1 Down Up mcd LD0 SCHLCCH1 ChLiv stVal CH1LIV Ethernet channel 1 live 1 Live mcd LD0 SCHLCCH2 ChLiv stVal CH2LIV Ethernet channel 2 live 1 Live mcd LD0 SCHLCCH3 ChLiv stVal CH3LIV Ethernet channel 3 live 1 Live mcd 2 3 2 3 LD0 DIAGLCCH1 Ethernet supervision 1 Table 79 LD0 DIAGLCCH1 Ethernet supervision 1 BitA RegA IEC 61850 name SA name Description Values LD0 DIAGLCCH1 ChLiv stVal CHLIV Etherne...

Страница 54: ...rm 1 Alarm mcd Wrn stVal WARNING Warning 1 Warning mcd 2 3 2 6 LD0 LDPRLRC1 Load profile record 1 Table 82 LD0 LDPRLRC1 Load profile record 1 BitA RegA IEC 61850 name SA name Description Value LD0 LDPRLRC1 MemWrn stVal Recording memory warning 1 Warning mcd MemAlm stVal Recording memory alarm 1 Alarm mcd 2 3 2 7 LD0 MAPGAPC7 Multipurpose protection 7 Table 83 LD0 MAPGAPC7 Multipurpose protection 7...

Страница 55: ...1 Start mcd Op general OPERATE Stage operate 1 Operate mcd 2 3 2 10 LD0 MAPGAPC10 Multipurpose protection 10 Table 86 LD0 MAPGAPC10 Multipurpose protection 10 BitA RegA IEC 61850 name SA name Description Values LD0 MAPGAPC10 Str general START Stage start 1 Start mcd Op general OPERATE Stage operate 1 Operate mcd 2 3 2 11 LD0 MAPGAPC11 Multipurpose protection 11 Table 87 LD0 MAPGAPC11 Multipurpose ...

Страница 56: ...start 1 Start mcd Op general OPERATE Stage operate 1 Operate mcd 2 3 2 14 LD0 MAPGAPC14 Multipurpose protection 14 Table 90 LD0 MAPGAPC14 Multipurpose protection 14 BitA RegA IEC 61850 name SA name Description Values LD0 MAPGAPC14 Str general START Stage start 1 Start mcd Op general OPERATE Stage operate 1 Operate mcd 2 3 2 15 LD0 MAPGAPC15 Multipurpose protection 15 Table 91 LD0 MAPGAPC15 Multipu...

Страница 57: ...ral START Stage start 1 Start mcd Op general OPERATE Stage operate 1 Operate mcd 2 3 2 18 LD0 MAPGAPC18 Multipurpose protection 18 Table 94 LD0 MAPGAPC18 Multipurpose protection 18 BitA RegA IEC 61850 name SA name Description Values LD0 MAPGAPC18 Str general START Stage start 1 Start mcd Op general OPERATE Stage operate 1 Operate mcd 2 3 2 19 LD0 RESTCTR1 Io CT supervision 1 Table 95 LD0 RESTCTR1 ...

Страница 58: ...Warning 1 Warning mcd 2 3 2 22 LD0 SPCGAPC1 Generic control point 16 pcs 1 Table 98 LD0 SPCGAPC1 Generic control point 16 pcs 1 BitA RegA IEC 61850 name SA name Description Values LD0 SPCGAPC1 SPCSO1 stVal Ouput state 1 0 1 Off On mcd SPCSO2 stVal Ouput state 2 0 1 Off On mcd SPCSO3 stVal Ouput state 3 0 1 Off On mcd SPCSO4 stVal Ouput state 4 0 1 Off On mcd SPCSO5 stVal Ouput state 5 0 1 Off On m...

Страница 59: ... mcd SPCSO16 stVal Ouput state 16 0 1 Off On mcd 2 3 2 23 LD0 TRPPTRC3 Master trip 3 Table 99 LD0 TRPPTRC3 Master trip 3 BitA RegA IEC 61850 name SA name Description Values LD0 TRPPTRC3 Op general Op input signal 1 Operate mcd Tr general Trip output signal 1 Trip mcd 2 3 2 24 LD0 TRPPTRC4 Master trip 4 Table 100 LD0 TRPPTRC4 Master trip 4 BitA RegA IEC 61850 name SA name Description Values LD0 TRP...

Страница 60: ... The alternatives are u16 u32 unsigned 16 and 32 bits integer or i16 i32 signed 16 and 32 bit integer Scale Scale factor as default Also an adjustable offset value exists that is set to 0 by default IEC 61850 name Original IED data object identification Described in the IEC 61850 format as Logical Device Logical Node and thereafter Data Object Data Attribute Logical Node is the same as the applica...

Страница 61: ...ngle bit 8005 Confirm register single bit 2 4 1 3 Control structure 2 Table 106 Control structure 2 RegA Type Scale IEC 61850 name SA name Description Values 8006 Execute register 1 8007 Password reg 1 acc to setting 8008 Password reg 2 acc to setting 8009 Control register single bit 8010 Confirm register single bit 2 4 1 4 Control structure 3 Table 107 Control structure 3 RegA Type Scale IEC 6185...

Страница 62: ...024 Control register single bit 8025 Confirm register single bit 2 4 1 7 Control structure 6 Table 110 Control structure 6 RegA Type Scale IEC 61850 name SA name Description Values 8026 Execute register 1 8027 Password reg 1 acc to setting 8028 Password reg 2 acc to setting 8029 Control register single bit 8030 Confirm register single bit 2 4 1 8 Control structure 7 Table 111 Control structure 7 R...

Страница 63: ...e Table 114 Event record structure RegA Type Scale IEC 61850 name SA name Description Values Selection write 9250 u16 1 Num of multiple records 1 10 9251 i16 1 Read selection 499 3 Record 1 data to read 9252 u16 1 Record sequence num 1 9999 9253 u16 1 Unread records left 0 499 Timestamp of record 9254 u16 1 Year Month Year Month 9255 u16 1 Day Hour Day Hour 9256 u16 1 Minute Second Min Sec 9257 u1...

Страница 64: ...1 Unread records left 0 499 Timestamp of record 9276 u16 1 Year Month Year Month 9277 u16 1 Day Hour Day Hour 9278 u16 1 Minute Second Min Sec 9279 u16 1 Millisecond Millisecond 9280 u16 1 Event identification 1 9281 u16 1 Data object ID1 1 9282 u16 1 Data object ID2 1 9283 u16 1 Event data value 1 1 9284 u16 1 Event data value 2 1 Record 4 data to read If selected 9285 u16 1 Record sequence num 1...

Страница 65: ...306 u16 1 Event data value 2 1 Record 6 data to read If selected 9307 u16 1 Record sequence num 1 9999 9308 u16 1 Unread records left 0 499 Timestamp of record 9309 u16 1 Year Month Year Month 9310 u16 1 Day Hour Day Hour 9311 u16 1 Minute Second Min Sec 9312 u16 1 Millisecond Millisecond 9313 u16 1 Event identification 1 9314 u16 1 Data object ID1 1 9315 u16 1 Data object ID2 1 9316 u16 1 Event d...

Страница 66: ...econd Millisecond 9335 u16 1 Event identification 1 9336 u16 1 Data object ID1 1 9337 u16 1 Data object ID2 1 9338 u16 1 Event data value 1 1 9339 u16 1 Event data value 2 1 Record 9 data to read If selected 9340 u16 1 Record sequence num 1 9999 9341 u16 1 Unread records left 0 499 Timestamp of record 9342 u16 1 Year Month Year Month 9343 u16 1 Day Hour Day Hour 9344 u16 1 Minute Second Min Sec 93...

Страница 67: ...le 115 Fault record structure header RegA Type Scale IEC 61850 name SA name Description Values Selection write 9401 i16 1 Read selection 99 3 Record data header 9402 u16 1 Record sequence num 0 65535 9403 u16 1 Unread records left 0 99 Timestamp of record 9404 u16 1 Year month Year Month 9405 u16 1 Day hour Day Hour 9406 u16 1 Minute second Min Sec 9407 u16 1 Millisecond Millisecond 9408 u16 1 Tim...

Страница 68: ...t 9422 u16 1000 Max50DifAA mag Max diff current phs A 0 000 80 00 0 pu 9423 u16 1000 Max50DifAB mag Max diff current phs B 0 000 80 00 0 pu 9424 u16 1000 Max50DifAC mag Max diff current phs C 0 000 80 00 0 pu 9425 u16 1000 Max50RstAA mag Max bias current phs A 0 000 50 000 pu 9426 u16 1000 Max50RstAB mag Max bias current phs B 0 000 50 000 pu 9427 u16 1000 Max50RstAC mag Max bias current phs C 0 0...

Страница 69: ... In 9445 u16 1000 APsSeq1 mag Current Ps Seq 1 0 000 50 000 In 9446 u16 1000 ANgSeq1 mag Current Ng Seq 1 0 000 50 000 In 9447 u16 1000 PhVPhsA1 mag Voltage phs A 1 0 000 4 000 Un 9448 u16 1000 PhVPhsB1 mag Voltage phs B 1 0 000 4 000 Un 9449 u16 1000 PhVPhsC1 mag Voltage phs C 1 0 000 4 000 Un 9450 u16 1000 PPVPhsAB1 mag Voltage phs AB 1 0 000 4 000 Un 9451 u16 1000 PPVPhsBC1 mag Voltage phs BC 1...

Страница 70: ...t Io 2 0 000 50 000 In 9471 u16 1000 AResClc2 mag Current Io Calc 2 0 000 50 000 In 9472 u16 1000 APsSeq2 mag Current Ps Seq 2 0 000 50 000 In 9473 u16 1000 ANgSeq2 mag Current Ng Seq 2 0 000 50 000 In 9474 u16 1000 PhVPhsA2 mag Voltage phs A 2 0 000 4 000 Un 9475 u16 1000 PhVPhsB2 mag Voltage phs B 2 0 000 4 000 Un 9476 u16 1000 PhVPhsC2 mag Voltage phs C 2 0 000 4 000 Un 9477 u16 1000 PPVPhsAB2 ...

Страница 71: ...ck in local time mode read and write synchronize Table 117 Protection relay s real time clock in local time mode read and write synchronize RegA Type Scale IEC 61850 name SA name Description Values 9201 Control register 0 21 9202 Year 2000 2999 9203 Month 1 12 9204 Day 1 31 9205 Hour 0 23 9206 Minute 0 59 9207 Second 0 59 9208 Millisecond 0 999 1 See the technical manual 2 4 1 15 Protection relay ...

Страница 72: ...01 170 14 Bit Indication bit 2734 0x170E 170 15 Bit Indication bit 2735 0x170F 171 00 Bit Indication bit 2736 0x1710 2 4 1 17 SSR1 System status register 1 device health Table 120 SSR1 System status register 1 device health RegA Type Scale IEC 61850 name SA name Description Values 128 00 Bit Device global error 1 Error 128 01 Bit Device global warning 1 Warning 128 02 Bit reserved 0 128 03 Bit res...

Страница 73: ...served 0 129 13 Bit reserved 0 129 14 Bit reserved 0 129 15 Bit reserved 0 2 4 1 19 SSR3 System status register 3 data available 1 client dependent Table 122 SSR3 System status register 3 data available 1 client dependent RegA Type Scale IEC 61850 name SA name Description Values 130 00 Bit Unread event records available 1 Available 130 01 Bit Unread fault records available 1 Available 130 02 Bit r...

Страница 74: ...category 6 has changed 1 Changed 131 06 Bit Data category 7 has changed 1 Changed 131 07 Bit Data category 8 has changed 1 Changed 131 08 Bit Data category 9 has changed 1 Changed 131 09 Bit Data category 10 has changed 1 Changed 131 10 Bit Data category 11 has changed 1 Changed 131 11 Bit Data category 12 has changed 1 Changed 131 12 Bit Data category 13 has changed 1 Changed 131 13 Bit Data cate...

Страница 75: ... number 0 15 133 12 Bit bit 0 133 13 Bit bit 1 133 14 Bit bit 2 133 15 Bit bit 3 1 See the technical manual 2 4 1 23 System diagnostic values Table 126 System diagnostic values RegA Type Scale IEC 61850 name SA name Description Values LD0 LPHD1 2060 u16 1 PhyHealth1 stVal Warning Last warning code 1 2061 u16 1 PhyHealth2 stVal Internal fault Last internal fault code 1 DR RDRE1 2062 u16 1 FltNum st...

Страница 76: ...y 1 31 9224 u16 1 Hour 0 23 9225 u16 1 Minute 0 59 9226 u16 1 Second 0 59 9227 u16 1 Millisecond 0 999 9228 u16 1 Reset reason 9228 0 Bit bit 0 1 Cold start 9228 1 Bit bit 1 1 Watchdog 9228 2 Bit bit 2 1 Warm start 2 4 1 25 User definable bits Alt 2 visible on 0x 1x 3x and 4x Table 128 User definable bits Alt 2 visible on 0x 1x 3x and 4x BitA Type Scale IEC 61850 name SA name Description Values 0 ...

Страница 77: ...le 131 LD0 ARCSARCx1 Arc protection RegA Type Scale IEC 61850 name SA name Description Values LD0 ARCSARC11 2054 u16 1 FACntRs stVal Fault arc 1 counter 0 65535 LD0 ARCSARC21 2055 u16 1 FACntRs stVal Fault arc 2 counter 0 65535 LD0 ARCSARC31 2056 u16 1 FACntRs stVal Fault arc 3 counter 0 65535 2 4 1 29 LD0 CMMXU1 Phase current demand values 1 Table 132 LD0 CMMXU1 Phase current demand values 1 RegA...

Страница 78: ... B amplitude 0 00 50 0 xIn 2016 Year month 2017 Day hour 2018 Minute second 2019 Milliseconds 2020 Time quality 2021 u16 1000 A phsC cVal mag Max demand IL2 Phs C amplitude 0 00 50 0 xIn 2022 Year month 2023 Day hour 2024 Minute second 2025 Milliseconds 2026 Time quality LD0 CMIMMXU1 Min demand values u16 1000 A phsA cVal mag Max demand IL1 Phs A amplitude 0 00 50 0 xIn u16 1000 A phsB cVal mag Ma...

Страница 79: ...2 Demand value 2027 u16 1000 AvAmpsA mag I_DMD_A Phs A amplitude 0 00 40 0 xIn 2028 u16 1000 AvAmpsB mag I_DMD_B Phs B amplitude 0 00 40 0 xIn 2029 u16 1000 AvAmpsC mag I_DMD_C Phs C amplitude 0 00 40 0 xIn Update time stamp See doc 2030 u16 Year month 2031 u16 Day hour 2032 u16 Minute second 2033 u16 Milliseconds 2034 u16 Time quality 2035 u16 1000 MaxAmpsA mag Max demand IL1 Max phs A demand 0 0...

Страница 80: ...current 2 152 u16 1000 A phsA instCVal mag I_INST_A Phs A amplitude 0 00 40 0 xIn 153 u16 1000 A phsB instCVal mag I_INST_B Phs B amplitude 0 00 40 0 xIn 154 u16 1000 A phsC instCVal mag I_INST_C Phs C amplitude 0 00 40 0 xIn 2 4 1 33 LD0 CSMSQI1 Sequence current measurement 1 Table 136 LD0 CSMSQI1 Sequence current measurement 1 RegA Type Scale IEC 61850 name SA name Description Values LD0 CSMSQI1...

Страница 81: ...measurement demand values 1 Table 138 LD0 PEMMXU1 Power measurement demand values 1 RegA Type Scale IEC 61850 name SA name Description Values LD0 PEAVMMXU1 Demand value 1939 i32 1 TotW mag Active power P high 999 999 1940 Low word 1941 i32 1 TotVAr mag Reactive power Q high 999 999 1942 Low word 1943 i32 1 TotVA mag Apparent power S high 999 999 1944 Low word 1945 i16 1000 TotPF mag Power factor 1...

Страница 82: ...factor 1 1 2 4 1 37 LD0 RESCMMXU1 Residual current demand value 1 Table 140 LD0 RESCMMXU1 Residual current demand value 1 RegA Type Scale IEC 61850 name SA name Description Values LD0 RCAVMMXU1 Demand value 1989 u16 1000 A res cVal mag I_DMD_RES Residual amplitude 0 00 50 0 xIn 1990 Year month 1991 Day hour 1992 Minute second 1993 Milliseconds 1994 Time quality LD0 RCMAMMXU1 Max demand value 1995 ...

Страница 83: ... amplitude 0 00 40 0 xIn Update time stamp 1 1966 u16 Year month 1967 u16 Day hour 1968 u16 Minute second 1969 u16 Milliseconds 1970 u16 Time quality 1971 u16 1000 MaxAmps mag Max demand Io Max Io demand 0 00 40 0 xIn Update time stamp 1 1972 u16 Year month 1973 u16 Day hour 1974 u16 Minute second 1975 u16 Milliseconds 1976 u16 Time quality 1 See the technical manual 2 4 1 40 LD0 RESCMMXU2 Residua...

Страница 84: ... amplitude 0 00 4 0 xUn 2 4 1 42 LD0 RESVMMXU1 Residual voltage measurement 1 Table 145 LD0 RESVMMXU1 Residual voltage measurement 1 RegA Type Scale IEC 61850 name SA name Description Values LD0 RESVMMXU1 Residual voltage 1 137 u16 1000 A res instCVal mag U0_INST amplitude 0 00 4 00 xUn 2 4 1 43 LD0 SSCBR1 Circuit breaker condition monitoring 1 Table 146 LD0 SSCBR1 Circuit breaker condition monito...

Страница 85: ...ND Est time to deactivate block 0 60000 s 2 4 1 45 LD0 TPOSYLTC1 Tap changer position indication 1 Table 148 LD0 TPOSYLTC1 Tap changer position indication 1 RegA Type Scale IEC 61850 name SA name Description Values LD0 TPOSYLTC1 151 i16 1 TapPos valWTr posVal TAP_POS Tap changer position 64 63 2 4 1 46 LD0 TR2PTDF1 Stabilized and instantaneous differential protection for two winding transformers 1...

Страница 86: ... amplitude 0 00 4 00 xUn 162 u16 1000 PPV phsCA cVal mag U_DB_CA Phs CA amplitude 0 00 4 00 xUn 2 4 1 48 LD0 VMMXU1 Voltage demand values 1 Table 151 LD0 VMMXU1 Voltage demand values 1 RegA Type Scale IEC 61850 name SA name Description Values LD0 VAVMMXU1 Demand value 1954 u16 1000 PhV phsA cVal mag U_DMD_A Phs A amplitude 0 00 4 0 Un 1955 u16 1000 PhV phsB cVal mag U_DMD_B Phs B amplitude 0 00 4 ...

Страница 87: ... input 4 in ohms 10000 00 2 4 1 51 LD0 XRGGIO130 RTD input values Table 154 LD0 XRGGIO130 RTD input values RegA Type Scale IEC 61850 name SA name Description Values LD0 XRGGIO130 2091 i16 1 AnIn1 mag AI_VAL1 RTD input 1 in ohms 10000 00 2092 i16 1 AnIn2 mag AI_VAL2 RTD input 2 in ohms 10000 00 2093 i16 1 AnIn3 mag AI_VAL3 RTD input 3 in ohms 10000 00 2094 i16 1 AnIn4 mag AI_VAL4 RTD input 4 in ohm...

Страница 88: ...2 3 LD0 LLN0 LPHD1 LDEV1 System values Table 157 LD0 LLN0 LPHD1 LDEV1 System values RegA Type Scale IEC 61850 name SA name Description Values LD0 LLN0 u16 1 ParChgCnt stVal Num of setting changes 0 65535 2 4 2 4 LD0 MDSOPT1 Runtime counter for machines and devices 1 Table 158 LD0 MDSOPT1 Runtime counter for machines and devices 1 RegA Type Scale IEC 61850 name SA name Description Values LD0 MDSOPT...

Страница 89: ...Analog value scaling 2 Table 161 LD0 SCA4GAPC2 Analog value scaling 2 RegA Type Scale IEC 61850 name SA name Description Values LD0 SCA4GAPC2 i16 1000 AnValOut1 mag AO1_VALUE Analog value 1 after scaling 0 N i16 1000 AnValOut2 mag AO2_VALUE Analog value 2 after scaling 0 N i16 1000 AnValOut3 mag AO3_VALUE Analog value 3 after scaling 0 N i16 1000 AnValOut4 mag AO4_VALUE Analog value 4 after scalin...

Страница 90: ...ute Logical Node is the same as the application function block name SA name The signal may have a defined label that is visible for example in the Application Configuration tool in PCM600 Description Short description of the signal See the technical manual for more information Value Meaning of the written value 2 5 1 Reset acknowledge and trigger points Table 165 Reset acknowledge and trigger poin...

Страница 91: ...x demands 1 Reset 2 5 2 CTRL CBCSWI1 Circuit breaker control 1 Table 166 CTRL CBCSWI1 Circuit breaker control 1 0xA CS IEC 61850 name SA name Description Values CTRL CBCSWI1 2048 1 00 Pos Oper ctlVal Select open 1 Select 2049 1 01 Pos Oper ctlVal Select close 1 Select 2050 1 02 Pos Oper ctlVal Cancel selection 1 Cancel 2051 1 03 Pos Oper ctlVal Execute selection 1 Execute 2052 1 04 Pos Oper ctlVal...

Страница 92: ...5 7 11 Pos Oper ctlVal Direct close 1 Close 2 5 5 CTRL ESXSWI1 Earthing switch control 1 Table 169 CTRL ESXSWI1 Earthing switch control 1 0xA CS IEC 61850 name SA name Description Values CTRL ESXSWI1 2054 1 06 Pos Oper ctlVal Select open 1 Select 2055 1 07 Pos Oper ctlVal Select close 1 Select 2056 1 08 Pos Oper ctlVal Cancel selection 1 Cancel 2057 1 09 Pos Oper ctlVal Execute selection 1 Execute...

Страница 93: ...10 control 0 1 Off On 2122 5 10 SPCS11 ctlVal Output 11 control 0 1 Off On 2123 5 11 SPCS12 ctlVal Output 12 control 0 1 Off On 2124 5 12 SPCS13 ctlVal Output 13 control 0 1 Off On 2125 5 13 SPCS14 ctlVal Output 14 control 0 1 Off On 2126 5 14 SPCS15 ctlVal Output 15 control 0 1 Off On 2127 5 15 SPCS16 ctlVal Output 16 control 0 1 Off On 2 5 8 LD0 SPCGAPC2 Generic control point 16 pcs 2 The binary...

Страница 94: ...flop 1 1 Reset 2097 4 01 Rs2 Oper ctlVal Reset flip flop 2 1 Reset 2098 4 02 Rs3 Oper ctlVal Reset flip flop 3 1 Reset 2099 4 03 Rs4 Oper ctlVal Reset flip flop 4 1 Reset 2100 4 04 Rs5 Oper ctlVal Reset flip flop 5 1 Reset 2101 4 05 Rs6 Oper ctlVal Reset flip flop 6 1 Reset 2102 4 06 Rs7 Oper ctlVal Reset flip flop 7 1 Reset 2103 4 07 Rs8 Oper ctlVal Reset flip flop 8 1 Reset 2 5 10 LD0 SRGAPC2 Se...

Страница 95: ...scription Value LD0 LLN0 MeasStatRs Oper ctlVal Reset all min and max demands 1 Reset LD0 LLN0 PQRs Oper ctlVal Reset all power quality data 1 Reset LD0 FLTRFRC1 RcdRs Oper ctlVal Reset fault record data 1 Reset 1MRS756878 H Section 2 Modbus data mappings RET615 89 Point List Manual ...

Страница 96: ...90 ...

Страница 97: ...ication and modeling IED Intelligent electronic device LED Light emitting diode LHMI Local human machine interface Modbus A serial communication protocol developed by the Modicon company in 1979 Originally used for communication in PLCs and RTU devices PCM600 Protection and Control IED Manager 1MRS756878 H Section 3 Glossary RET615 91 Point List Manual ...

Страница 98: ...92 ...

Страница 99: ...93 ...