V
1
2
A
GUID-31DF5495-91F1-4A4B-8FD5-50625038961E V1 EN
Figure 20:
Testing a trip contact
1 Trip contact under test
2 Current limiting resistor
•
To check the status of the output circuits driving the output relay via the LHMI, select
Main menu/Tests/I/O modules
and then navigate to the board with the actual binary
output to be checked.
•
Test and change the relay state manually.
1MRK 505 293-UUS A
Section 8
Troubleshooting
131
Commissioning manual