Fault indication
Additional information
Internal Fault
TRM-Error
A TRM card error has occurred. The
instance number is displayed at the end
of the fault indication.
Internal Fault
COM-Error
A COM card error has occurred. The
instance number is displayed at the end
of the fault indication.
Internal Fault
PSM-Error
A PSM card error has occurred. The
instance number is displayed at the end
of the fault indication.
8.2.2
Warnings
The warning message associated with the fault is found in the internal event list in the
LHMI menu
Main menu/Diagnostics/Internal events
. The message includes the date,
time, description and signal state for the fault. The current status of the internal fault
signals can also be checked via the LHMI in
Main menu/Diagnostics/IED status/
General
.
When a fault appears, record the fault indication message and state it when ordering
service.
Table 5:
Warning indications
Warning indication
Additional information
Warning
IEC 61850 Error
IEC 61850 has not succeeded
in some actions such as
reading the configuration file,
startup etc.
Warning
DNP3 Error
Error in DNP3 communication.
8.2.3
Additional indications
The additional indication messages do not activate internal fault or warning.
The messages are listed in the LHMI menu under the event list. The signal status data is
found under the IED status and in the internal event list.
Table 6:
Additional indications
Warning indication
Additional information
Time Synch Error
Source of the time synchronization is lost or time
system has made a time reset.
Settings Changed
Settings have been changed.
Setting Groups Changed
Setting group has been changed.
Section 8
1MRK 505 293-UUS A
Troubleshooting
128
Commissioning manual