I.L. 40-385.1B
iv
(5/92)
• All features listed as standard for the Non-Pilot
MDAR V2.00 are included in the Pilot system
• Independent pilot phase and ground distance
units
• Permissive Overreach Transfer Trip (POTT) /
Simplified Unblocking
• Permissive Underreach Transfer Trip (PUTT)
• Directional Comparison Blocking Scheme (BLK)
• POTT or Simplified Unblocking Weakfeed
• • Instantaneous Forward Directional Overcurrent
Function for High Resistance Ground Fault Sup-
plement to Overreach Pilot, with adjustable timer
(from 0 to 15) in 1 cycle steps or Block
• Instantaneous Reverse Directional Overcurrent
Ground Function
– Carrier Ground Start on Blocking Scheme
– Weakfeed System Application
• • Reclose Block on Breaker Failure (BF) Squelch
• 3-Terminal Line Application
• Weakfeed Trip
Features Included in Version V2.00
The following features are
standard for the Pilot MDAR V2.00:
Features Included in Version V2.00
The following features are
optional for the Non-Pilot and the Pilot MDAR V2.00:
• Optional communications attachment
RS232C/PONI
INCOM/PONI
• • Optional
16 sets of oscillographic data and intermediate
target data. Each set includes 7 analog graphic
inputs and 24 digital intermediate targets with 8
samples per cycle. Each analog input contains 1
prefault and 7 fault cycles. (Data collection can be
started by TRIP, Z2PU, Z2Z3 or
∆
V
∆
I depending
on the setting of OSC.)
• Optional FT-14 switches
• Optional Out-of-Step Block
• Optional Single-Pole-Trip (SPT) logic and out-
puts:
– SPT/RI1 on first
φ
GF and 3PT on other fault
types.
– 3PT/RB if reclosing on a permanent fault.
– 3PT/RB if second phase(s) fault during single
phasing.
– 3PT on a time delay limit (o.35-5.0 sec in 0.05
sec steps) if the system fails to reclose (62T).
• Optional OSC Settings (trip or
∆
V
∆
I)
• Optional TRIP/RI mode selector for:
TTYP SET AT
TRIP
RI
OFF
3PT
NO
1PR
3PT
RI2 (
φ
G)
2PR
3PT
RI2 (
φ
G,
φφ
G)
3PR
3PT
RI2 (
φ
G, M
φ
)
SPR
SPT (
φ
G)
RI1
3PT (M
φ
)
N0
SR3R
SPT (
φ
G)
RI1
3PT (M
φ
)
RI2
SPT
=
Single Pole Trip
3PT
=
3 Pole Trip
RI
=
Reclose Initiate
RB
=
Reclose Block
RI2
=
3 Pole Reclose Initiate
RI1
=
Single Pole Reclose Initiate
φ
G
=
Single Phase-to-Ground Faults
M
φ
=
Multi-Phase Faults
φφ
=
2-Phase Faults
Содержание REL-300
Страница 30: ......
Страница 32: ......
Страница 33: ......
Страница 38: ......
Страница 39: ......
Страница 40: ......
Страница 41: ......
Страница 42: ......
Страница 43: ......
Страница 44: ......
Страница 45: ......
Страница 62: ......
Страница 63: ......
Страница 64: ......
Страница 65: ......
Страница 66: ......
Страница 67: ......
Страница 68: ......
Страница 69: ......
Страница 70: ......
Страница 71: ......
Страница 72: ......
Страница 73: ......
Страница 74: ......
Страница 75: ......
Страница 76: ......
Страница 77: ......
Страница 86: ......
Страница 87: ......
Страница 88: ......
Страница 116: ...I L 40 385 1B 6 14 5 92 Figure 6 1 Test Connection for Single Phase to Ground Faults Sheet 1 of 4...
Страница 117: ...I L 40 385 1B 5 92 6 15 Figure 6 2 Test Connection for Three Phase Faults 1502B51 Sub 1 Sheet 2 of 4...
Страница 118: ...I L 40 385 1B 6 16 5 92 Figure 6 3 Test Connection for Phase to Phase Faults 1502B51 Sub 1 Sheet 3 of 4...
Страница 131: ......
Страница 132: ......
Страница 133: ......
Страница 134: ......
Страница 135: ...I L 40 385 1B SD 6 5 92 Figure SD 2 MDAR Block Diagram sheet 1 of 1 Sub 1 1611C12...