I.L. 40-385.1B
6-4
(5/92)
The reclose contacts (RI2-1 and RI2-2) should be
closed for setting of TTYP = 2PR or 3PR, and should
be open for TTYP = OFF or 1PR.
Step 14. Repeat Step 13 for both BC and CA faults.
Use the following voltages for each fault type:
BC CA
V
V
V
V
V
V
1.1.6
Zone 2 Tests
Step 15. Press the DISPLAY SELECT pushbutton
until the SETTINGS mode LED is displayed.
Change the setting values to:
• Z1P
= “OUT” (Zone 1 phase value)
• Z1G
= “OUT” (Zone 1 ground distance)
• Z2P
= 4.5
Ω
(Zone 2 phase value)
• T2P
= 1.0 sec (Zone 2 phase timer)
• Z2G
= 4.5
Ω
(Zone 2 ground value)
• T2G
= 1.5 sec (Zone 2 ground timer)
• Z2RI = “YES” (Zone 2 reclosing)
• TTYP = “3PR”
(Reclosing mode)
Step 16. Perform Steps 10 thru 14 (above) for Zone
2 only, using delayed trip times according to the
zone 2 phase timer (T2P), and the Zone 2 ground
timer (T2G). Tolerances for T2P and T2G are 5%
for an input current that is 10% above the calcu-
lated value.
Repeat Step 10.The RI2 contacts 1 and 2 should
be closed, and the RB contacts 1 and 2 should be
open. Reset Z2RI to “NO”.
Repeat Step 10 again. The RI2 contacts 1 and 2
should be open and the RB contacts 1 and 2
should be closed.
Change the settings of T2G and T2P to BLK.
Zone 2 should not be tripped for any type of fault.
1.1.7
Zone 3 Tests
Step 17. Press the DISPLAY SELECT pushbutton
until the SETTINGS mode LED is displayed.
Change the setting values to:
• Z2P
= “OUT” (Zone 2 phase value)
• Z2G
= “OUT” (Zone 2 ground distance)
• Z3P
= 4.5
Ω
(Zone 3 phase value)
• T3P
= 2.0 sec (Zone 3 phase timer)
• Z3G
= 4.5
Ω
(Zone 3 ground value)
• T3G
= 2.5 sec (Zone 3 ground timer)
• Z3FR = “FWD” (Zone 3 direction)
• Z3RI = “YES” (RI = Z3T)
• TTYP = “3PR” (Reclosing Mode)
Step 18. Perform preceding steps 10 thru 14 for
Zone 3 only, using delayed trip times according
to the Zone 3 phase timer (T3P), and the Zone 3
ground timer (T3G). Tolerances for T3P and T3G
are
±
5% for an input current that is 10% above
the calculated value.
Repeat Step 10. The RI2 contacts 1 and 2 should
be closed, and the RB contacts 1 and 2 should be
open. Reset Z3RI to “NO”.
Repeat Step 10 again. The RI2 contacts 1 and 2
should be open and the RB contacts 1 and 2
should be closed.
Step 19. Set Z3FR = REV, then repeat Step 10, ex-
cept apply AG reversed fault (i.e., I
a
leads Van by
105
°
). The relay should trip, at I
a
= 4.2A, in 2.5
seconds. Reset Z3FR to “FWD”.
NOTE: For customers who use a computer to
test the relays, or use their own settings
for maintenance, refer to the following
example to calculate and determine trip
currents; set the relay as follows:
Z1P = ZIG = 4.5
T1 = 0
Z2P = Z2G = 6.0
T2P= T2G = 0.2
Z3P = Z3G = 9.0
T3P= T3G = 0.3
PANG = GANG = 75o
ZR
= 3
a. Single-Phase-to-Ground Fault
Use the equation in Step 10, and the following input
voltages:
V
AN
96.4 120
°
∠
=
V
AN
17.3
120
°
–
∠
=
V
BN
17.3 0
°
∠
=
V
BN
96.4 120
°
∠
=
V
CN
17.3
120
°
–
∠
=
V
CN
17.3 0
°
∠
=
I
F
3.33
45
°
–
∠
=
I
F
3.33
45
°
–
∠
=
V
AN
45 0
°
∠
V
LN
=
=
V
BN
70
120
°
–
∠
=
V
CN
70 120
°
∠
=
Содержание REL-300
Страница 30: ......
Страница 32: ......
Страница 33: ......
Страница 38: ......
Страница 39: ......
Страница 40: ......
Страница 41: ......
Страница 42: ......
Страница 43: ......
Страница 44: ......
Страница 45: ......
Страница 62: ......
Страница 63: ......
Страница 64: ......
Страница 65: ......
Страница 66: ......
Страница 67: ......
Страница 68: ......
Страница 69: ......
Страница 70: ......
Страница 71: ......
Страница 72: ......
Страница 73: ......
Страница 74: ......
Страница 75: ......
Страница 76: ......
Страница 77: ......
Страница 86: ......
Страница 87: ......
Страница 88: ......
Страница 116: ...I L 40 385 1B 6 14 5 92 Figure 6 1 Test Connection for Single Phase to Ground Faults Sheet 1 of 4...
Страница 117: ...I L 40 385 1B 5 92 6 15 Figure 6 2 Test Connection for Three Phase Faults 1502B51 Sub 1 Sheet 2 of 4...
Страница 118: ...I L 40 385 1B 6 16 5 92 Figure 6 3 Test Connection for Phase to Phase Faults 1502B51 Sub 1 Sheet 3 of 4...
Страница 131: ......
Страница 132: ......
Страница 133: ......
Страница 134: ......
Страница 135: ...I L 40 385 1B SD 6 5 92 Figure SD 2 MDAR Block Diagram sheet 1 of 1 Sub 1 1611C12...