I.L. 40-385.1B
4-10
(5/92)
Displayed at
Function Field
Value Field
Information/Settings
(using 5 A ct and 60 Hz)
(SEE NOTE ON SHEET 3)
Software version
VERS
numerical (0,1)
Oscillographic data initiation
OSC *
TRIP/Z2TR/Z2Z3/
∆
V
∆
I
Fault data initiation
FDAT
TRIP/Z2TR/Z2Z3
ct ratio
CTR
30-5000 (5)
PT ratio
VTR
300-7000 (10)
Rated freq.
FREQ
60, 50
ct secondary rating
CTYP
5 or 1
Enable/disable readouts
in primary I & V values
RP
YES/NO
Reactance for fault location
(ohms per unit distance)
XPUD
0.300-1.500, in 0.001/DTYP
Fault location, displayed in km or miles
DTYP
KM or MI (miles)
Reclosing mode
TTYP
1. 3PT on all faults, no RI
OFF
2. 3PT on all faults, with 3RI on
φ
GF
1PR
3. 3PT on all faults, with 3RI on
φ
GF/2
φ
F
2PR
4. 3PT on all faults, w/3RI
3PR
5. SPT on
φ
GF with SRI
3PT on M
φ
F without RI
SPR
6. SPT on
φ
GF with SRI
3PT on M
φ
F with 3RI
SR3R
Single phasing limit timer
62T *
0.300-5000, in 0.050 sec. steps
RI on Z1T
Z1RI
YES/NO
RI on Z2T
Z2RI
YES/NO
RI ON Z3T
Z3RI
YES/NO
Breaker Failure Reclose block
BFRB *
YES/NO
Pilot logic control
PLT *
YES/NO
Pilot system selection:
STYP
1. Non-Pilot, 3-zone distance
3ZNP
2. Zone-1 extension
Z1E
3. Permissive overreach transfer trip
or unblocking
POTT
4. Permissive underreach transfer trip
PUTT
5. Blocking
BLK
Forward Direction Ground Timer
FDGT *
BLK, 0 to 15 cycles in 1cycle steps
Weakfeed Enable
WFEN *
YES/NO
3-Terminal Line Application
3TRM *
YES/NO
Blocking system channel
coordination timer
BLKT *
0-98, in 2 ms steps
Reverse block sw.
RBSW *
Omitted
Pilot phase setting
PLTP *
OUT, 0.01-50.00 in 0.01
Ω
steps
Pilot ground setting
PLTG *
OUT, 0.01-50.00 in 0.01
Ω
steps
*Optional
TABLE 4-1. SETTING DISPLAY
(SHEET 1 OF 3)
Содержание REL-300
Страница 30: ......
Страница 32: ......
Страница 33: ......
Страница 38: ......
Страница 39: ......
Страница 40: ......
Страница 41: ......
Страница 42: ......
Страница 43: ......
Страница 44: ......
Страница 45: ......
Страница 62: ......
Страница 63: ......
Страница 64: ......
Страница 65: ......
Страница 66: ......
Страница 67: ......
Страница 68: ......
Страница 69: ......
Страница 70: ......
Страница 71: ......
Страница 72: ......
Страница 73: ......
Страница 74: ......
Страница 75: ......
Страница 76: ......
Страница 77: ......
Страница 86: ......
Страница 87: ......
Страница 88: ......
Страница 116: ...I L 40 385 1B 6 14 5 92 Figure 6 1 Test Connection for Single Phase to Ground Faults Sheet 1 of 4...
Страница 117: ...I L 40 385 1B 5 92 6 15 Figure 6 2 Test Connection for Three Phase Faults 1502B51 Sub 1 Sheet 2 of 4...
Страница 118: ...I L 40 385 1B 6 16 5 92 Figure 6 3 Test Connection for Phase to Phase Faults 1502B51 Sub 1 Sheet 3 of 4...
Страница 131: ......
Страница 132: ......
Страница 133: ......
Страница 134: ......
Страница 135: ...I L 40 385 1B SD 6 5 92 Figure SD 2 MDAR Block Diagram sheet 1 of 1 Sub 1 1611C12...