Verification of the
ACCALARM
value and time delay to operation
1. Connect the test set for the injection of three-phase currents and three-phase
voltages to the appropriate current and voltage terminals of the IED.
2. Ensure that the settings in the IED are appropriate for the default settings,
especially the
CurrStartLevel
,
FreqHighLimit
,
FreqLowLimit
,
UHighLimit
and
ULowLimit
setting.
3. Supply the IED with three-phase currents and voltages at their rated value.
4. Slowly decrease the frequency of the applied voltage until it crosses the
frequency high limit and the
START
signal appears.
5. Continuously change the frequency of the applied voltage, so that for a certain
time the frequency is outside the set band limit and falls gradually within the band
limit.
6. Count only the time when the frequency lies within the set frequency band limit.
Wait for a time corresponding to
tAccLimit
and ensure that the
ACCALARM
signal
appears.
7. Measure the time delay for the
ACCALARM
signal and compare it to the set value.
Extended testing
1. To check the value of
TRIPACC
, repeat the above test case in such a way that the
frequency of the applied voltage is within the set frequency band when time
approaches the
tAccLimit
setting value.
Verification of generator start and stop logic
1. Ensure that the settings in the IED are appropriate to the default settings,
especially the
CurrStartLevel
,
FreqHighLimit
,
FreqLowLimit
,
UHighLimit
and
ULowLimit
.
2. Ensure that the setting
CBCheck
is enabled.
3. Supply the IED with three-phase currents and voltages at their rated values.
4. Slowly decrease the frequency of the applied voltage until the
START
signal
appears.
5. Activate the
CBOPEN
input signal.
6. Slowly decrease the injected current below the
CurrStartLevel
value until the
START
signal disappears.
7. Compare the current magnitude value to the set value.
Verification of voltage band limit check logic
1. Ensure that the settings in the IED are appropriate to the default settings,
especially the
CurrStartLevel
,
FreqHighLimit
,
FreqLowLimit
,
UHighLimit
and
ULowLimit
settings.
2. Ensure that the
EnaVoltCheck
is enabled.
3. Supply the IED with three-phase currents and voltages at their rated values.
4. Check that the
VOLTOK
signal appears.
5. Slowly decrease the frequency of the applied voltage until the
START
signal
appears.
Section 12
1MRK502053-UEN B
Testing functionality by secondary injection
192
Generator protection REG670 2.0 IEC
Commissioning manual
Содержание REG670 2.0 IEC
Страница 1: ...Relion 670 series Generator protection REG670 2 0 IEC Commissioning manual ...
Страница 2: ......
Страница 16: ...10 ...
Страница 30: ...24 ...
Страница 58: ...52 ...
Страница 62: ...56 ...
Страница 76: ...70 ...
Страница 90: ...84 ...
Страница 94: ...88 ...
Страница 108: ...102 ...
Страница 246: ...240 ...
Страница 252: ...246 ...
Страница 267: ...261 ...