en06000498.vsd
REG 670
RXTTE 4
I
U
230 V AC
120 V AC
0
Generator rotor winding
G
313
314
315
421
428
324
325
221 222
Optional
external resistor
Connection to be done
by the panel builder
IEC06000498 V1 EN
Figure 42:
Ten times amplification of current via a current transformer
The test described in steps
can be done with the generator at stand-still
situations.
Procedure
1.
The test should be prepared with a switch connected between the output of
RXTTE4 (221) and the station earth. Initially this switch is open.
2.
First the 120 (230) V input to RXTTE4 is disconnected. This should give a signal
from REG670 that the injection voltage is low.
3.
Reconnect the 120 (230) V input and check that the low injection voltage signal
resets.
1MRK502053-UEN B
Section 12
Testing functionality by secondary injection
Generator protection REG670 2.0 IEC
147
Commissioning manual
Содержание REG670 2.0 IEC
Страница 1: ...Relion 670 series Generator protection REG670 2 0 IEC Commissioning manual ...
Страница 2: ......
Страница 16: ...10 ...
Страница 30: ...24 ...
Страница 58: ...52 ...
Страница 62: ...56 ...
Страница 76: ...70 ...
Страница 90: ...84 ...
Страница 94: ...88 ...
Страница 108: ...102 ...
Страница 246: ...240 ...
Страница 252: ...246 ...
Страница 267: ...261 ...