7. After more than 5 seconds increase the measured voltage back to the value
slightly below
USealIn
level. MAINFUF signal should not reset.
8. Slowly increase measured voltage to the value slightly above
USealIn
until
MAINFUF signal resets.
9. Record the measured voltage and compare with the set value
USealIn
.
12.9.3.1
Completing the test
Continue to test another function or end the test by changing the
TestMode
setting to
Off
. Restore connections and settings to their original values, if they were changed for
testing purposes.
12.10
Control
12.10.1
Synchrocheck, energizing check, and synchronizing
SESRSYN
This section contains instructions on how to test the synchrocheck, energizing check,
and synchronizing function SESRSYN for single, double and 1½ breaker
arrangements.
Prepare the IED for verification of settings outlined in section
section
in this chapter.
At commissioning and periodical checks, the functions shall be tested with the used
settings. To test a specific function, it might be necessary to change some setting
parameters, for example:
•
AutoEnerg
=
Off
/
DLLB
/
DBLL
/
Both
•
ManEnerg
=
Off
•
Operation
=
Off
/
On
•
Activation of the voltage selection function if applicable
The tests explained in the test procedures below describe the settings, which can be
used as references during testing before the final settings are specified. After testing,
restore the equipment to the normal or desired settings.
A secondary injection test set with the possibility to alter the phase angle and
amplitude of the voltage is needed. The test set must also be able to generate different
frequencies on different outputs.
The description below applies for a system with a nominal frequency
of 50 Hz but can be directly applicable to 60 Hz. SESRSYN can be set
Section 12
1MRK502053-UEN B
Testing functionality by secondary injection
202
Generator protection REG670 2.0 IEC
Commissioning manual
Содержание REG670 2.0 IEC
Страница 1: ...Relion 670 series Generator protection REG670 2 0 IEC Commissioning manual ...
Страница 2: ......
Страница 16: ...10 ...
Страница 30: ...24 ...
Страница 58: ...52 ...
Страница 62: ...56 ...
Страница 76: ...70 ...
Страница 90: ...84 ...
Страница 94: ...88 ...
Страница 108: ...102 ...
Страница 246: ...240 ...
Страница 252: ...246 ...
Страница 267: ...261 ...