X1+XN
X
R (Ohm/loop)
50%
80%
1
2
3
4
5
6
7
8
9
10
11
80% of RLdFw
40% of RLdFw
RFPE
12
13
c
b =
Ar
gLD
alt. 80% of
RFPE (Load
encroachment)
120°
20°
a
IEC05000369-3-en.vsd
IEC05000369 V3 EN
Figure 34:
Distance protection characteristic with test points for phase-to-earth
measurements
is used in conjunction with figure
Table 15:
Test points for phase-to-earth L3-E (Ohm/Loop)
Test point
Reach
Value
Comments
1
X
(2 x X1
set
+X0
set
)/3
R
0
2
X
(2 x X1
set
+ X0
set
)/3
R
2 x R1
set
+ R0
set
)/3
3
X
0.8 x (2 x X1
set
+ X0
set
)/3
R
0.8 x (2 x R1
set
+ R0
set
)/3 +RFPE
set
4
X
0.5 x (2 x X1
set
+ R0
set
)/3
R
0.5 x (2 x R1
set
+R0
set
)/3 + RFPE
set
5
X
0.85 x RFPE
set
x tan(ArgLdset)
ArgLd = angle for the maximal load
transfer
R
0.85 x RFPE
6
X
RLdFwset x tan(ArgLdSet)
R
RLdFw
set
7
X
0
R
RLdFw
set
8
X
–02143 x RLdFw
set
Exact: 0.8 x RFPE x tan (ArgDir=20°)
R
0.8 x RLdFw
set
9
X
–0.8 x RLdFw
set
x tan(ArgDir=20°)
R
0.8 x RLdFw
set
Table continues on next page
1MRK502053-UEN B
Section 12
Testing functionality by secondary injection
Generator protection REG670 2.0 IEC
117
Commissioning manual
Содержание REG670 2.0 IEC
Страница 1: ...Relion 670 series Generator protection REG670 2 0 IEC Commissioning manual ...
Страница 2: ......
Страница 16: ...10 ...
Страница 30: ...24 ...
Страница 58: ...52 ...
Страница 62: ...56 ...
Страница 76: ...70 ...
Страница 90: ...84 ...
Страница 94: ...88 ...
Страница 108: ...102 ...
Страница 246: ...240 ...
Страница 252: ...246 ...
Страница 267: ...261 ...