I
I
I
I
A
s
CTs
CTp
50
50
10459
1
9000
1 162
=
×
=
×
=
.
EQUATION14059 V1 EN
(Equation 19)
∠
I
50s
=0°
frequency of I
50s
= 50 Hz
It
I
I
I
A
fs
CTs
CTp
tf
=
×
=
×
=
10459
1
9000
1 162
.
EQUATION14062 V1 EN
(Equation 20)
∠
I
tfs
=0°
frequency of I
tfs
= 50 Hz
•
Check that the service values (VOLTAGE, CURRENT, R(%), X(%)) are
according to the injected quantities and that ROTORANG is close to 0 rad.
For this particular injection the service values are:
•
VOLTAGE = 13.12 kV
•
CURRENT = 20918 A
•
R = 9.01%
•
X = 65.27%
•
ROTORANG = 0.04 rad
Note that these values identify a point outside the lens characteristic, even if it is close
to the point RE. Neither START nor TRIP is issued.
Execution of the dynamic test
The test may be performed by using two states of a sequence tool that is a basic feature
of test sets.
•
State 1: pre-test condition.
Steady voltage and current are applied in order to get a steady high impedance.
This is a point in the plane R-X that is far away from the lens characteristic. Define
the following three-phase symmetrical quantities (the phase angle is related to
phase L1):
V
V
V
V
V
ts
t FwdZ
VT s
VT p
=
×
×
=
×
×
=
1 1
1 1 11931
0 1
13 8
95 1
.
.
.
.
.
,
,
,
EQUATION14057 V1 EN
(Equation 21)
∠
=
=
=
V
ForwardX
ForwardR
ts
arctan
arctan
.
.
59 33
8 19
82..14
°
EQUATION14058 V1 EN
(Equation 22)
frequency of V
ts
= 50 Hz
I
50s
=0 A
I
tfs
=0 A
•
State 2: main test step.
Section 12
1MRK502053-UEN B
Testing functionality by secondary injection
128
Generator protection REG670 2.0 IEC
Commissioning manual
Содержание REG670 2.0 IEC
Страница 1: ...Relion 670 series Generator protection REG670 2 0 IEC Commissioning manual ...
Страница 2: ......
Страница 16: ...10 ...
Страница 30: ...24 ...
Страница 58: ...52 ...
Страница 62: ...56 ...
Страница 76: ...70 ...
Страница 90: ...84 ...
Страница 94: ...88 ...
Страница 108: ...102 ...
Страница 246: ...240 ...
Страница 252: ...246 ...
Страница 267: ...261 ...