The fibre optic LON bus is implemented using either glass core or plastic core fibre
optic cables.
Table 6:
Specification of the fibre optic connectors
Glass fibre
Plastic fibre
Cable connector
ST-connector
snap-in connector
Cable diameter
62.5/125 m
1 mm
Max. cable length
1000 m
10 m
Wavelength
820-900 nm
660 nm
Transmitted power
-13 dBm (HFBR-1414)
-13 dBm (HFBR-1521)
Receiver sensitivity
-24 dBm (HFBR-2412)
-20 dBm (HFBR-2521)
9.2.1
The LON Protocol
The LON protocol is specified in the LonTalkProtocol Specification Version 3 from
Echelon Corporation. This protocol is designed for communication in control
networks and is a peer-to-peer protocol where all the devices connected to the network
can communicate with each other directly. For more information of the bay-to-bay
communication, refer to the section Multiple command function.
9.2.2
Hardware and software modules
The hardware needed for applying LON communication depends on the application,
but one very central unit needed is the LON Star Coupler and optical fibres connecting
the star coupler to the IEDs. To interface the IEDs from the MicroSCADA with
Classic Monitor, application library LIB520 is required.
The HV Control 670 software module is included in the LIB520 high-voltage process
package, which is a part of the Application Software Library in MicroSCADA
applications.
The HV Control 670 software module is used for control functions in the IEDs. The
module contains a process picture, dialogues and a tool to generate a process database
for the control application in MicroSCADA.
When using MicroSCADA Monitor Pro instead of the Classic Monitor, SA LIB is
used together with 670 series Object Type files.
The HV Control 670 software module and 670 series Object Type
files are used with both 650 and 670 series IEDs.
Use the LON Network Tool (LNT) to set the LON communication. This is a software
tool applied as one node on the LON bus. To communicate via LON, the IEDs need
to know
Section 9
1MRK502053-UEN B
Establishing connection and verifying the LON communication
90
Generator protection REG670 2.0 IEC
Commissioning manual
Содержание REG670 2.0 IEC
Страница 1: ...Relion 670 series Generator protection REG670 2 0 IEC Commissioning manual ...
Страница 2: ......
Страница 16: ...10 ...
Страница 30: ...24 ...
Страница 58: ...52 ...
Страница 62: ...56 ...
Страница 76: ...70 ...
Страница 90: ...84 ...
Страница 94: ...88 ...
Страница 108: ...102 ...
Страница 246: ...240 ...
Страница 252: ...246 ...
Страница 267: ...261 ...