For the test as motor the frequency current may have 50.5 Hz in the
quadrant 1 and 2 of the R-X plane and 49.5 Hz in the quadrant 3 and
4.
Verifying the settings by secondary injection
It is advised to connect the analog output channels of the function block OOSPPAM
to the internal disturbance recorder (and in particular to the function block A4RADR)
in order to perform a better analysis of the tests.
If the device is in test mode, the recording of the disturbances are enabled by the
setting in
Main menu/Settings/IED Settings/Monitoring/Disturbance report/
DisturbanceReport/DRPRDRE:1:
set the parameter
OpModeTest
to
On
.
1. Check the Application Configuration: verify that hardware voltage and current
channels of the IED are properly connected to SMAI function blocks, and that the
proper analog outputs of SMAI’s are connected to the analog inputs of the
function block OOSPPAM.
2. Connect three-phase voltage channels of the test set to the appropriate IED
terminals.
3. Connect in parallel two groups of three-phase currents of the test set to the
appropriate IED terminals.
4. Connect the appropriate trip output of the IED to the input channel of the test set
that monitors the trip.
5. Go to
Main menu/Settings/IED Settings/Impedance protection/
OutOfStep(78,Ucos)/OOSPPAM(78,Ucos):1
, and make sure that the function
is enabled, that is,
Operation
is set to
On
.
12.4.5.2
Test of point RE (R
FwdR
, X
FwdX
)
The trajectory of the impedance does not enter the lens characteristic.
Preliminary steady state test at 50 Hz
•
Go to
Main menu/Test/Function status/Impedance protection/
OutOfStep(78,Ucos)/OOSPPAM(78,Ucos):1/Outputs
to check the available
service values of the function block OOSPPAM.
•
Apply the following three-phase symmetrical quantities (the phase angle is
related to phase L1):
V
V
V
V
V
ts
t FwdZ
VT s
VT p
=
×
×
=
×
×
=
1 1
1 1 11931
0 1
13 8
95 1
.
.
.
.
.
,
,
,
EQUATION14057 V1 EN
(Equation 17)
∠
=
=
=
V
ForwardX
ForwardR
ts
arctan
arctan
.
.
59 33
8 19
82..14
°
EQUATION14058 V1 EN
(Equation 18)
frequency of V
ts
= 50 Hz
1MRK502053-UEN B
Section 12
Testing functionality by secondary injection
Generator protection REG670 2.0 IEC
127
Commissioning manual
Содержание REG670 2.0 IEC
Страница 1: ...Relion 670 series Generator protection REG670 2 0 IEC Commissioning manual ...
Страница 2: ......
Страница 16: ...10 ...
Страница 30: ...24 ...
Страница 58: ...52 ...
Страница 62: ...56 ...
Страница 76: ...70 ...
Страница 90: ...84 ...
Страница 94: ...88 ...
Страница 108: ...102 ...
Страница 246: ...240 ...
Страница 252: ...246 ...
Страница 267: ...261 ...