P1
P3
P4
X
R
LineAngle
ZxFwd
ZxRev
P2
IEC11000313-1-en.vsd
IEC11000313 V2 EN
Figure 41:
Proposed four test points for phase-to-earth fault
Where,
ZxFwd
is the forward positive sequence impedance setting for zone x (where, x is 2- 3
depending on the zone selected)
ZxRev
is the reverse positive sequence impedance setting for zone x (where x is 2- 3
depending on the zone selected)
LineAngle
is the Impedance angle for phase-to-phase fault in degrees
Test points
X
R
P1
ZxFwd · sin(LineAngle)
ZxFwd · cos(LineAngle)
P2
((
ZxFwd -ZxRev / 2) · sin(LineAngle))
ZxFwd / 2 · (1 + cos(LineAngle) + ZxRev/2
· (1 – cos(
LineAngle))
P3
((
ZxFwd -ZxRev / 2) · sin(LineAngle))
-
ZxFwd / 2 · (1 – cos(LineAngle) + ZxRev /
2 · (1 + cos(
LineAngle))
P4
-
ZxRev · sin(LineAngle)
-
ZxRev · cos(LineAngle)
Change the magnitude and angle of phase-to-phase voltage to achieve impedances at
test points P1, P2, P3 and P4. For each test point, observe that the output signals,
START and STZx are activated (where x is 2 or 3 depending on selected zone). After
the operate time delay of the respective zone has elapsed, also the signals TRIP and
TRZx (where x is 2 or 3 depending on selected zone) shall be activated.
Section 12
1MRK502053-UEN B
Testing functionality by secondary injection
144
Generator protection REG670 2.0 IEC
Commissioning manual
Содержание REG670 2.0 IEC
Страница 1: ...Relion 670 series Generator protection REG670 2 0 IEC Commissioning manual ...
Страница 2: ......
Страница 16: ...10 ...
Страница 30: ...24 ...
Страница 58: ...52 ...
Страница 62: ...56 ...
Страница 76: ...70 ...
Страница 90: ...84 ...
Страница 94: ...88 ...
Страница 108: ...102 ...
Страница 246: ...240 ...
Страница 252: ...246 ...
Страница 267: ...261 ...