ABB i-bus
®
KNX
Device technology
SUG/U 1.1 | 2CDC508171D0201 7
2
Device technology
SUG/U 1.1
The Split Unit Gateway converts KNX
commands to infrared commands which
are used to manage climate control
equipment (split units).
The device is installed near the split unit
in a flush-mounted or wall-mounted box.
The transmission diode in the supplied
cable is bonded to the receiver of the split
unit itself.
The device is supplied with power via
the KNX bus voltage; no additional
power supply is required.
2.1
Technical data
Power supply
Supply voltage
Via ABB i-bus
®
KNX (21...31 V DC)
Power loss P
Max. 0.4 W
Current consumption
Max. 12 mA
Connections
KNX
Bus connection terminal, screwless
IR cable connection socket
Plug-in terminal
IR cable
Length 2 m
Operating and display elements
Red LED and button
For assignment of the physical address
Protection degree
IP 20 in the installed state
Compliant to EN 60 529
Protection class
III
To EN 61 140
Isolation category
Overvoltage category
III according to EN 60 664-1
Pollution degree
2 to EN 60 664-1
KNX safety extra low voltage
SELV 30 V DC
Temperature range
Operation
-5 °C…+45 °C
Storage
-25…+55°C
Transport
-25…+70 °C
Ambient conditions
Maximum air humidity
95 %, no condensation allowed
Atmospheric pressure
Atmosphere up to 2,000 m
Design
Dimensions
39 x 40 x 12 mm (H x W x D)
Installation
In a wall box
Flush-mounted or wall-mounted
Mounting position
any
Weight
0.02 kg
Housing, color
Plastic, halogen free, gray
Approvals
KNX to EN 50 090-1, -2
CE marking
In accordance with the EMC directive and low
voltage directive
2C
D
C
0
71
00
6F
001
7
Содержание i-bus KNX SUG/U 1.1
Страница 1: ...ABB i bus KNX SUG U 1 1 Split Unit Gateway Product Manual ...
Страница 2: ......
Страница 4: ......
Страница 12: ...ABB i bus KNX Device technology 10 2CDC508171D0201 SUG U 1 1 2 3 Dimension drawing 2CDC072018F0016 ...
Страница 52: ...ABB i bus KNX Appendix 50 2CDC508171D0201 SUG U 1 1 A 4 Notes ...
Страница 53: ...ABB i bus KNX Appendix SUG U 1 1 2CDC508171D0201 51 Notes ...
Страница 54: ...ABB i bus KNX Appendix 52 2CDC508171D0201 SUG U 1 1 Notes ...
Страница 55: ......