ABB i-bus
®
KNX
Commissioning
42 2CDC508171D0201 | SUG/U 1.1
No.
Function
Group object name
Data type
Flags
21
Setpoint temperature
Split unit
2 byte
DPT 9.001
C, W
Dependent on parameters
Always visible
The Split Unit Gateway receives the setpoint value via this group object.
If when the Setpoint temperature limit is parametrized and activated the gateway receives setpoint values outside the
parametrized range, it sets the setpoint temperature to the upper or lower limit of the range.
If you activate Setpoint temperature limit while the current setpoint temperature is outside the setpoint temperature range,
the setpoint temperature will be set to the upper or lower limit of the range.
22
Status Setpoint temperature
Split unit
2 byte
DPT 9.001
C, R, T
Dependent on parameter
Enable group object "Status setpoint temperature" 2 bytes
This object indicates the current setpoint value.
23
Setpoint temperature up/down
Split unit
1 bit
DPT 1.007
C, W
Dependent on parameter
Always visible
This object increases or reduces the setpoint temperature by intervals of 1 kelvin.
1 = Setpoint temperature increases
0 = Setpoint temperature decreases
If the temperature reaches the upper or lower setpoint temperature limit, further telegrams have no effect.
24
Deactivate Setpoint temperature limit
Split unit
1 bit
DPT 1.003
C, W
Dependent on parameter
Limit Setpoint temperature range
This object activates/deactivates the setpoint temperature limit
1 = Setpoint temperature limit deactivated
0 = Setpoint temperature limit activated
If you activate Setpoint temperature limit while the current setpoint temperature is outside the setpoint temperature range,
the setpoint temperature will be set to the upper or lower limit of the range.
The setpoint temperature limit is activated after download.
However, activating the Forced operation priority takes the setpoint temperature limit into account.
Содержание i-bus KNX SUG/U 1.1
Страница 1: ...ABB i bus KNX SUG U 1 1 Split Unit Gateway Product Manual ...
Страница 2: ......
Страница 4: ......
Страница 12: ...ABB i bus KNX Device technology 10 2CDC508171D0201 SUG U 1 1 2 3 Dimension drawing 2CDC072018F0016 ...
Страница 52: ...ABB i bus KNX Appendix 50 2CDC508171D0201 SUG U 1 1 A 4 Notes ...
Страница 53: ...ABB i bus KNX Appendix SUG U 1 1 2CDC508171D0201 51 Notes ...
Страница 54: ...ABB i bus KNX Appendix 52 2CDC508171D0201 SUG U 1 1 Notes ...
Страница 55: ......