Commissioning
26 2CDC508171D0201 | SUG/U 1.1
3.2.3
Functions parameter window
Function priorities are as follows:
1)
Forced operation
2)
Window contact
3)
Presence, scenes, boost and group objects without priority
If several priorities are activated at once, the highest priority is executed.
The lower priorities are updated in the background and only executed once the higher priority is
deactivated.
While a priority is active, Presence and Scene are still evaluated, but Boost and other non-priority group
objects are discarded.
Timers (switching off delay, monitoring time) start immediately.
Enable "Forced operation" function
Options:
No
Yes
•
Yes
: Enables the 1-bit group object
Forced operation
.
This enables the corresponding parameter window.